| 2009-09-23 17:56:13 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 20047 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PROVIDE WIND RESISTANCE DATA FOR ALL OUTDOOR |
| | APPLIANCES AND EQUIPMENT WHICH IS EXPOSED TO WIND SUCH |
| | AS RTU, EXHAUST FANS, VENTS AND REMOTE CONDENSERS IN |
| | ACCORDANCE WITH FBC-M 301.12. |
| | |
| | 2. PROVIDE MOTORIZED VOLUME DAMPERS WITH SHUTOFF DAMPER |
| | CONTROLS ON OUTSIDE AIR INTAKES IN ACCORDANCE WITH |
| | FBC-B 13-409.AB 3.3. |
| | |
| | 3. THE TYPE I HOOD SYSTEM SHALL BE DESIGNED AND |
| | INSTALLED TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN |
| | WHENEVER COOKING OPERATIONS OCCUR IN ACCORDANCE WITH |
| | FBC-M 507.2.1.1. THE ACTIVATION OF THE EXHAUST FAN |
| | SHALL OCCUR THROUGH AN INTERLOCK WITH THE COOKING |
| | APPLIANCES, BY MEANS OF HEAT SENSORS OR BY MEANS OF |
| | OTHER APPROVED METHODS. SHOW THE METHOD TO BE USED ON |
| | PLANS. |
| | |
| | 4. UPDATE WIND RESISTANCE NOTES ON PAGE M5.0 DETAILS TO |
| | REFERENCE CURRENT REFERENCE STANDARDS AS LISTED IN THE |
| | 2007 FBC WITH 2009 SUPPLEMENT. EXAMPLE: ASCE7-05 IS THE |
| | CURRENT STANDARD FOR WIND DESIGN. |
| | |
| | 5. PAGE A3.0 CALLS FOR RTU CONDENSATE TO BE DISCHARGED |
| | TO A MOP SINK. CONDENSATE SHALL NOT BE DISCHARGED INTO |
| | THE SANITARY SEWER SYSTEM PER CITY ORDINANCE. |
| | CONDENSATE MAY BE DISCHARGED INTO STORM WATER DRAINAGE |
| | SYSTEM OR OTHER APPROVED LOCATION IN ACCORDANCE WITH |
| | FBC-M 307.2.1. |
| | |
| | 6. PLEASE CORRECT HVAC NOTE #10 ON PAGE M1.0 TO |
| | CORRESPOND WITH FLOOR PLAN WHICH CALLS FOR SMOKE |
| | DETECTORS TO BE INSTALLED ON THE SUPPLY IN ACCORDANCE |
| | WITH FBC-M 606.2.1. |
| | |
| | 7. RTU'S SHALL BE PROVIDED WITH AUXILIARY DRAIN |
| | PROTEXTION VIA WATER LEVEL DETECTION DEVICE IN |
| | ACCORDANCE WITH FBC-M 307.2.3.1. |
| | |
| | NOTE: SEPARATE PERMITS ARE REQUIRED FOR EACH OF THE |
| | FOLLOWING: HOOD, HOOD SUPPRESSION SYSTEM, WALK-IN |
| | COOLER/FREEZER. ONCE PLANS ARE CODE COMPLIANT, AN |
| | APPLICATION FOR HOOD PERMIT MAY BE SUBMITTED BASED ON |
| | THESE PLANS. SEPARATE HOOD PLANS ARE NOT REQUIRED. |
| | HOWEVER, PROVIDE SEPARATE APPLICATIONS WITH PLANS AND |
| | FULL DOCUMENTATION FOR BOTH THE HOOD SUPPRESSION SYSTEM |
| | AND THE WALK-IN COOLER. |
| | |