Plan Review Notes
Plan Review Notes For Permit 09090440
Permit Number 09090440
Review Stop M
Sequence Number 1
Notes
Date Text
2009-09-23 17:56:13REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 20047 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE WIND RESISTANCE DATA FOR ALL OUTDOOR
 APPLIANCES AND EQUIPMENT WHICH IS EXPOSED TO WIND SUCH
 AS RTU, EXHAUST FANS, VENTS AND REMOTE CONDENSERS IN
 ACCORDANCE WITH FBC-M 301.12.
  
 2. PROVIDE MOTORIZED VOLUME DAMPERS WITH SHUTOFF DAMPER
 CONTROLS ON OUTSIDE AIR INTAKES IN ACCORDANCE WITH
 FBC-B 13-409.AB 3.3.
  
 3. THE TYPE I HOOD SYSTEM SHALL BE DESIGNED AND
 INSTALLED TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN
 WHENEVER COOKING OPERATIONS OCCUR IN ACCORDANCE WITH
 FBC-M 507.2.1.1. THE ACTIVATION OF THE EXHAUST FAN
 SHALL OCCUR THROUGH AN INTERLOCK WITH THE COOKING
 APPLIANCES, BY MEANS OF HEAT SENSORS OR BY MEANS OF
 OTHER APPROVED METHODS. SHOW THE METHOD TO BE USED ON
 PLANS.
  
 4. UPDATE WIND RESISTANCE NOTES ON PAGE M5.0 DETAILS TO
 REFERENCE CURRENT REFERENCE STANDARDS AS LISTED IN THE
 2007 FBC WITH 2009 SUPPLEMENT. EXAMPLE: ASCE7-05 IS THE
 CURRENT STANDARD FOR WIND DESIGN.
  
 5. PAGE A3.0 CALLS FOR RTU CONDENSATE TO BE DISCHARGED
 TO A MOP SINK. CONDENSATE SHALL NOT BE DISCHARGED INTO
 THE SANITARY SEWER SYSTEM PER CITY ORDINANCE.
 CONDENSATE MAY BE DISCHARGED INTO STORM WATER DRAINAGE
 SYSTEM OR OTHER APPROVED LOCATION IN ACCORDANCE WITH
 FBC-M 307.2.1.
  
 6. PLEASE CORRECT HVAC NOTE #10 ON PAGE M1.0 TO
 CORRESPOND WITH FLOOR PLAN WHICH CALLS FOR SMOKE
 DETECTORS TO BE INSTALLED ON THE SUPPLY IN ACCORDANCE
 WITH FBC-M 606.2.1.
  
 7. RTU'S SHALL BE PROVIDED WITH AUXILIARY DRAIN
 PROTEXTION VIA WATER LEVEL DETECTION DEVICE IN
 ACCORDANCE WITH FBC-M 307.2.3.1.
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR EACH OF THE
 FOLLOWING: HOOD, HOOD SUPPRESSION SYSTEM, WALK-IN
 COOLER/FREEZER. ONCE PLANS ARE CODE COMPLIANT, AN
 APPLICATION FOR HOOD PERMIT MAY BE SUBMITTED BASED ON
 THESE PLANS. SEPARATE HOOD PLANS ARE NOT REQUIRED.
 HOWEVER, PROVIDE SEPARATE APPLICATIONS WITH PLANS AND
 FULL DOCUMENTATION FOR BOTH THE HOOD SUPPRESSION SYSTEM
 AND THE WALK-IN COOLER.
  