Plan Review Notes
Plan Review Notes For Permit 09090440
Permit Number 09090440
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-25 14:08:15 
 1) NOTE: PLANS SHALL CONTAIN THE FOLLOWING CODES.
 2005 NFPA-70
 2006 NFPA-101
  
 PER FAC 69A-3.012, FBC 2007 WITH 2009 REVISIONS.
  
 ** AN EXAMPLE AND NEEDING THE CORRECTED CODES IS SHEET
 E2.1 STATES THE 2002 NEC FOR THE LOAD CALCULATIONS.
 DECEMBER 8, 2006 THE STATE OF FLORIDA ADOPTED THE 2005
 NEC.
  
  
 2) NOTE: PLEASE SUBMIT A COMPLETED FLA COM IN
 COMPLIANCE WITH 13-415.AB.5, 13-415.AB.2.2. THE
 EXTERIOR LIGHTING ON THE PLANS IS NOT COMPLETE FOR
 FIXTURES AND ITEMS SUCH AS THE SITE LIGHTING/PARKING
 LOT LIGHTING POLES ARE NOT COMPLETE ON PLANS.
 FOR EXAMPLE: THE FIXTURE LEGEND DOES NOT INDICATE THE
 TYPE OF SITE LIGHTS. THE INPUT DATA REPORT OF THE
 SUBMITTED ENERGY CALCULATIONS DO NOT CONTAIN ANY OF THE
 PARKING LOT LIGHT FIXTURES.
  
 3) NOTE: PLEASE SEE 230.70, 230.71 OF THE NEC. THE
 PLANS CONTAIN NOTES FOR THE NO MORE THAN 6 MEANS OF
 DISCONNECT HOWEVER THE EQUIPMENT AS SUBMITTED COULD
 ALLOW SIX ADDITIONAL SINGLE POLE BREAKERS WHICH WOULD
 BE IN VIOLATION OF THE 6 DISCONNECTING MEANS RULE.
 PLEASE INSTALL A SINGLE MEANS OF DISCONNECT IF USING
 THIS EQUIPMENT AS SHOWN/SUBMITTED.
 THE AHJ HAS SEEN NUMEROUS LOCATIONS WITH EQUIPMENT
 INSTALLED JUST LIKE THE ONE SHOWN WITH MORE THAN 6
 MEANS OF DISCONNECT.
 ** THE ONLY OTHER OPTION IS THE EQUIPMENT AS SHOWN
 WOULD BE REQUIRED TO CONTAIN A PERMANENT DEAD-FRONT
 WHICH NOT ALLOW THE INSTALLATION OF ANY OTHER BREAKERS.
  
 4) NOTE: PLEASE SEE FBC 13-415.AB.1.4 FOR TYPE OF
 EXTERIOR TIME CLOCK REQUIRED WHEN USING A TIME CLOCK.
 DETAIL FOR EXTERIOR TYPE CONTROLS DOES SHOW A
 PHOTO-SENSOR HOWEVER ONLY IF THE PHOTO-CELL WILL OVER
 RIDE ON AND OFF CONDITIONS AN ASTRONOMICAL TIME CLOCK
 WILL NOT BE REQUIRED.
 ** PLEASE PROVIDE LIGHTING CONTACTOR SCHEDULE.
  
 5) NOTE: PLEASE PROVIDE SHOW WINDOW RECEPTACLES PER
 210.62. PLEASE BE SURE TO ADJUST LOAD CALCULATIONS PER
 220.43A
  
 6) NOTE: PLEASE SEE NEC 210.8B2 AS ALL 15/20 120
 RECEPTACLES IN KITCHEN AREAS SHALL BE GFI/ GFI
 PROTECTED. THIS IS REQUIRED WHETHER OR NOT THESE FEED
 DEDICATED EQUIPMENT OR COUNTER SPACE RECEPTACLES.
 ** PLANS CONTAIN A NOTE WHICH REFERENCES THE 2002 NEC
 WHICH WAS A DIFFERENT SECTION OF THE CODE. ALSO, PLEASE
 BE AWARE THAT BASED ON THE SYMBOL LEGEND ON PLANS MANY
 OF THESE DEVICES ARE NOT INDICATING GFI PROTECTION.
  
 7) NOTE: PLEASE SEE FBC 13-415.AB.1.1, .1.2 AND .1.3.
 THIS COMMENT DOES NOT HAVE ANYTHING TO DO WITH
 AUTOMATED LIGHTING CONTROLS IN A BUILDING GREATER THAN
 5K SQ FT. THE SECTIONS OF THE CODE STILL APPLY TO
 BUILDINGS SMALLER THAN 5K SQFT FOR SEPARATE SPACE
 CONTROLS.
 FOR EXAMPLE: ANY SPACES, ROOMS WHERE FLOOR TO CEILING
 WALLS SEPARATE SPACE REQUIRES SEPARATE CONTROLS.
 THE INFORMATION SHOWN ON PLANS DOES NOT PROVIDE ENOUGH
 INFORMATION FOR MEETING SECTIONS OF THE CODES GIVEN.
 PLANS DO NOT SHOW ANY SEPARATE CONTROLS IN SEPARATE
 ROOMS.
  
  
 ** IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  