| Date |
Text |
| 2009-09-25 14:08:15 | |
| | 1) NOTE: PLANS SHALL CONTAIN THE FOLLOWING CODES. |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | |
| | PER FAC 69A-3.012, FBC 2007 WITH 2009 REVISIONS. |
| | |
| | ** AN EXAMPLE AND NEEDING THE CORRECTED CODES IS SHEET |
| | E2.1 STATES THE 2002 NEC FOR THE LOAD CALCULATIONS. |
| | DECEMBER 8, 2006 THE STATE OF FLORIDA ADOPTED THE 2005 |
| | NEC. |
| | |
| | |
| | 2) NOTE: PLEASE SUBMIT A COMPLETED FLA COM IN |
| | COMPLIANCE WITH 13-415.AB.5, 13-415.AB.2.2. THE |
| | EXTERIOR LIGHTING ON THE PLANS IS NOT COMPLETE FOR |
| | FIXTURES AND ITEMS SUCH AS THE SITE LIGHTING/PARKING |
| | LOT LIGHTING POLES ARE NOT COMPLETE ON PLANS. |
| | FOR EXAMPLE: THE FIXTURE LEGEND DOES NOT INDICATE THE |
| | TYPE OF SITE LIGHTS. THE INPUT DATA REPORT OF THE |
| | SUBMITTED ENERGY CALCULATIONS DO NOT CONTAIN ANY OF THE |
| | PARKING LOT LIGHT FIXTURES. |
| | |
| | 3) NOTE: PLEASE SEE 230.70, 230.71 OF THE NEC. THE |
| | PLANS CONTAIN NOTES FOR THE NO MORE THAN 6 MEANS OF |
| | DISCONNECT HOWEVER THE EQUIPMENT AS SUBMITTED COULD |
| | ALLOW SIX ADDITIONAL SINGLE POLE BREAKERS WHICH WOULD |
| | BE IN VIOLATION OF THE 6 DISCONNECTING MEANS RULE. |
| | PLEASE INSTALL A SINGLE MEANS OF DISCONNECT IF USING |
| | THIS EQUIPMENT AS SHOWN/SUBMITTED. |
| | THE AHJ HAS SEEN NUMEROUS LOCATIONS WITH EQUIPMENT |
| | INSTALLED JUST LIKE THE ONE SHOWN WITH MORE THAN 6 |
| | MEANS OF DISCONNECT. |
| | ** THE ONLY OTHER OPTION IS THE EQUIPMENT AS SHOWN |
| | WOULD BE REQUIRED TO CONTAIN A PERMANENT DEAD-FRONT |
| | WHICH NOT ALLOW THE INSTALLATION OF ANY OTHER BREAKERS. |
| | |
| | 4) NOTE: PLEASE SEE FBC 13-415.AB.1.4 FOR TYPE OF |
| | EXTERIOR TIME CLOCK REQUIRED WHEN USING A TIME CLOCK. |
| | DETAIL FOR EXTERIOR TYPE CONTROLS DOES SHOW A |
| | PHOTO-SENSOR HOWEVER ONLY IF THE PHOTO-CELL WILL OVER |
| | RIDE ON AND OFF CONDITIONS AN ASTRONOMICAL TIME CLOCK |
| | WILL NOT BE REQUIRED. |
| | ** PLEASE PROVIDE LIGHTING CONTACTOR SCHEDULE. |
| | |
| | 5) NOTE: PLEASE PROVIDE SHOW WINDOW RECEPTACLES PER |
| | 210.62. PLEASE BE SURE TO ADJUST LOAD CALCULATIONS PER |
| | 220.43A |
| | |
| | 6) NOTE: PLEASE SEE NEC 210.8B2 AS ALL 15/20 120 |
| | RECEPTACLES IN KITCHEN AREAS SHALL BE GFI/ GFI |
| | PROTECTED. THIS IS REQUIRED WHETHER OR NOT THESE FEED |
| | DEDICATED EQUIPMENT OR COUNTER SPACE RECEPTACLES. |
| | ** PLANS CONTAIN A NOTE WHICH REFERENCES THE 2002 NEC |
| | WHICH WAS A DIFFERENT SECTION OF THE CODE. ALSO, PLEASE |
| | BE AWARE THAT BASED ON THE SYMBOL LEGEND ON PLANS MANY |
| | OF THESE DEVICES ARE NOT INDICATING GFI PROTECTION. |
| | |
| | 7) NOTE: PLEASE SEE FBC 13-415.AB.1.1, .1.2 AND .1.3. |
| | THIS COMMENT DOES NOT HAVE ANYTHING TO DO WITH |
| | AUTOMATED LIGHTING CONTROLS IN A BUILDING GREATER THAN |
| | 5K SQ FT. THE SECTIONS OF THE CODE STILL APPLY TO |
| | BUILDINGS SMALLER THAN 5K SQFT FOR SEPARATE SPACE |
| | CONTROLS. |
| | FOR EXAMPLE: ANY SPACES, ROOMS WHERE FLOOR TO CEILING |
| | WALLS SEPARATE SPACE REQUIRES SEPARATE CONTROLS. |
| | THE INFORMATION SHOWN ON PLANS DOES NOT PROVIDE ENOUGH |
| | INFORMATION FOR MEETING SECTIONS OF THE CODES GIVEN. |
| | PLANS DO NOT SHOW ANY SEPARATE CONTROLS IN SEPARATE |
| | ROOMS. |
| | |
| | |
| | ** IMPORTANT** |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |