2009-09-22 18:29:05BUILDING PLAN REVIEW
 PERMIT: 09090440
 ADD: 836 BELVEDERE RD
 CONT: CORPORATE PROPERTY SERVICES, INC.
 TEL: (954)426-5144
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE THE GEOTECHNICAL REPORT COMPLETED BY
 P. S. I. INC. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 2) THE TITLE SHEET T1.0 INDICATES IN THE INDEX THERE
 SHOULD BE A S2.0 FRAMING SHEET WHICH IS MISSING FROM
 BOTH SETS OF PLANS. SHEET S1.0 NOTE# 8 INDICATES THAT
 SHEET S2.0 HAS THE MASONRY PIER SCHEDULE, CAN'T BE
 REVIEWED AT THIS TIME, THERE MAY BE ADDITIONAL COMMENTS
 ONCE REVIEWED.
  
 3) SHEET S1.0 HAS TWO WALL SECTION DETAIL 7 SHEET S4.0
 AND DETAIL# 20 SHEET S4.2 AS WELL AS SHEET A5.0 WALL
 SECTION B ALL INDICATE STEMWALL CONSTRUCTION A
 CONSTRUCTION JOINT AND A SECONDARY POUR PLEASE REVIEW
 SECTION :
 EFIS COVERINGS. 2603.8.1 FOAM-PLASTIC INSULATION
 INCLUDING, BUT NOT LIMITED TO, EXTRUDED OR EXPANDED
 POLYSTYRENE OR POLYISOCYANURATE SHALL NOT BE INSTALLED
 BELOW GRADE ON FOUNDATION WALLS OR BELOW GRADE ON THE
 EXTERIOR OF SLAB FOUNDATIONS.
  
 4) SHEET S-3.0 VERSES M-5.0, THE STRUCTURAL SHEET
 INDICATES THE USE OF STEEL BAR JOIST WHERE AS THE M-5.0
 DETAILS INDICATE ALL THE MECHANICAL ROOF ATTACHMENTS
 BEING WOOD TRUSSES AND WOOD DECK PLEASE CORRECT FRAMING
 SUPPORT AND DECK DETAILS AND MECHANICAL EQUIPMENT
 ATTACHMENT DETAILS.
  
 5) SHEET S4.1 DETAILS 4 & 12 INDICATE THE TYPE OF WELD
 BUT NOT THE SIZE OF THE WELD, 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 6) SHEET A-1.0 VERSES TTHE ENERGY CALCS, THE PLANS CALL
 FOR ALL FILLED CELL /W FOAM VERSES THE ENERGY CALCS
 WHICH INDICATE 3/4INCH ISO INSULATION BETWEEN FURRING
 STRIPS, DISCEPANCY 106.1.1.
  
 7) CONTRACTORS OPTION: TO SUBMIT PRODUCT APPROVALS A
 THIS TIME OR BEFORE INSULATION OF PRODUCT BEFORE THE
 FRAMING INSPECTION, LIST OF PRODUCT APPROVALS REQUIRED
 BY RULE 9B-72:
 A) WINDOWS- STOREFRONT AND OPERABLE
 B) MULLIONS HORIZONTAL OR VERTICAL
 C) EXTERIOR DOORS GLAZED
 D) EXTERIOR DOORS METAL
 E) WALL LOUVERS
 F) EFIS WALL SYSTEMS
 G) ROOFING ASSEMBLIES
 H) PRE-ENGINEERED A/C STANDS
 I) STORM PANELS OR SHUTTERS IF WINDOWS ARE NOT TESTED
 TO LARGE MISSILE IMPACT RESISTANCE
  
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 8) ROOF TOP MECHANICAL EQUIPMENT: 301.13 FBC
 MECHANICAL. WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST WIND PRESSURES ON
 THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
 NOTE THIS DOES NOT ONLY MEAN TTHE ATTACHMENT OF THE
 UNIT TO THE BASE SUPPORT BUT THE EXTERIOR CABINET OF
 THE UNIT ITSELF. ENGINEERING LETTERS WILL SUFFICE.
  
 9A) PLEASE NOTE THE ROOFING PERMIT WILL BE A SEPERATE
 PERMIT AND WILL NEED TO INCLUDE THE PRODUCT APPROVAL,
 INDICATE WHICH SUB-SYSTEM TO BE INSTALLED ON THEIS
 PROJECT. IF A MIAMI-DADE NOA IS SUBMITTED IT MAY HAVE
 VARIOUS OPTIONS FOR FASTENING OF THE ROOFING PRODUCT
 AND INSULATION WITHIN EACH SUB-SYSTEM.
 EACH OPTION WILL HAVE IT OWN DESIGN PRESSURES. THE
 PRODUCT APPROVAL WILL ALSO STATE IF EACH SYSTEM CAN
 HAVE ENHANCED FASTENING (LIMITATION 7) OR LIMITATION 9
 WHICH DOES NOT ALLOW FOR ENHANCED FASTENING.
  
 9B) THE OTHER ISSUE YOU WILL NEED TO ADDRESS IS ROOF
 INSULATION, A MINIMUM R-VALUE OF R-22.3 WILL NEED TO BE
 OBTAINED ( ENERGY CALCULATION) . UNDER THE ROOFING
 PERMIT PLEASE PROVIDE A ROOF INSULATION PLAN.
  
 10) PLEASE ADDRESS THE ENERGY CALCULATIONS INPUT DATA
 REPORT INDICATES THE ROOF ASSEMBLY AS A WOOD DECK/
 TRUSSES AND A R-19 INSULATION. SEE CHAPTER 13 APPENDIX
 B TABLE B-19.
  
 11) ENERGY CALCULATION INPUT DATA REPORT- FLOORS-
 PLEASE REVIEW ALLOWABLE R-VALUES FOR FLOORING THE INPUT
 DATA REPORT INDICATES THEY ARE TAKING CREDIT FOR CARPET
 AND PADDING WHERE AS A7.0 INDICATES TILE FLOORS. PLEASE
 REVIEW CHAPTER 13 APPENDIX B SECTION B2.5.2 .1 MASS
 FLOORS AND R-VALUES.
  
 12) SHEET A3.0 PLEASE REVIEW ASCE-98 AND THE 2007 FBC
 CODE REFRENECES IN CHAPTER 35, ASCE 7-05 IS THE CURRENT
 REFRENCED STANDARD.
  
 13) SHEET A5.0 DETAIL B INDICATES AN EXTERIOR FRAMING
 SECTION WITH THE WORDING AT THE BOTTOM OF THE SECTION
 EFIS OVER 2X4 FRAMING OVER CMU. PLEASE REVIEW 2304.6
 ENCLOSED BUILDINGS SHALL BE SHEATHED WITH ONE OF THE
 MATERIALSOF THE NOMINAL THICKNESS SPECIFIED IN TABLE
 2304.6.
  
 14) SHEET A5.1 & A5.2 BOTH INDICATE A FINISHED WALL
 SEECTION AT THE TOWER , THERE IS NO SECTION OF FRAMING
 MEMBERS. PLEASE REVIEW SECTION:
  
 2304.11.2.4 SLEEPERS AND SILLS. SLEEPERS AND SILLS ON A
 CONCRETE OR MASONRY SLAB THAT IS IN DIRECT CONTACT WITH
 EARTH SHALL BE OF NATURALLY DURABLE OR
 PRESERVATIVE-TREATED WOOD.
  
 2304.11.2.6 WOOD SIDING. CLEARANCE BETWEEN WOOD SIDING
 AND EARTH ON THE EXTERIOR OF A BUILDING SHALL NOT BE
 LESS THAN 6 INCHES (152 MM) EXCEPT WHERE SIDING,
 SHEATHING AND WALL FRAMING ARE OF NATURALLY DURABLE OR
 PRESERVATIVE-TREATED WOOD.
  
 15) SHEET A5.1 ENTRY CANOPY IS INDICATED AS B.O. BY
 OTHERS, IS THIS MEAN IT IS INCLUDED UNDER THIS PERMIT
 BUT IS TO BE DESIGNED UNDER A SPECILITY ENGINEER?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 16) SHEET A6.4 DETAILS1 & 2 BOTH INDICATE MENU BOARD
 AND OR SOFFIT ATTACHMENTS TO WOOD TRUSES, PLEASE
 CORRECT DETAILS SHEET S3.0 INDICATES STEEL BAR JOIST.
 DISCREPANCY IN PLANS 106.1.1.
  
 17) SHEET ADA 1.1 AT THE FRONT OF THE BUILDING PLANS
 INDICATE A SINGLE DOOR PLEASE INDICATE THE BUILD OUTS
 ON EACH SIDE OF THE DOOR, PROVIDE THE WIDTH
 OF THE SIDE WALK AND INDICATE THE SIDE APPROACH FOR AN
 OUT SWING DOOR AS INDICATED IN FIGURE 25 (B)
 MANEUVERING CLEARENCES AT DOORS, SEE VALUES FOR X & Y.
  
 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved