 1. CONSTRUCTION, DEMOLITION AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. SUITABLE EXITS ARE TO BE PROVIDED DURING
 CONSTRUCTION.
  
 3. TRASH AND DEBRIS SHALL BE REMOVED DAILY.
  
 4. WHENEVER A REQUIRED FIRE SAFETY SYSTEM IS OUT OF
 SERVICE MORE THAN FOUR (4) HOURS IN A TWENTY FOUR (24)
 HOUR PERIOD A FIRE WATCH IS REQUIRED OR THE BUILDING
 MUST BE EVACUATED. ALL FIRE WATCH REQUESTS MUST BE IN
 WRITING TO THE BATTALION CHIEF OF FIRE PREVENTION OR
 THE ASSISTANT FIRE MARSHAL.
  
 5. ALL NEW FIRE DAMPERS AFTER INSTALLATION SHALL BE
 DROP TESTED TO ENSURE PROPER OPERATION.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER REMODEL.
  
 7. SEPARATE PLANS AND PERMITS FOR FIRE ALARM SYSTEM
 REMODEL.
  
 8. ALL NEW ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 9. NEW SOFFITS SHALL NOT INTERFERE WITH ANY FIRE
 SPRINKLER HEAD OPERATION..
  
 10. IS THERE ANY EXISTING SMOKE DETECTOR ABOVE THE FIRE
 ALARM CONTROL PANEL.
  
 11. ARE ELEVATOR WARNING SIGNS PROVIDED WITHIN THE
 ELEVATOR LOBBIES.
  
 12. NO FIRE STOPPING DETAILS PROVIDED.
  
 13. PLEASE DECLARE ON THE PLANS THAT THE BUILDING IS A
 HIGH-RISE BUILDING.
  
 14. PLEASE INDICATE NEW CEILING TILE FLAMESPREAD.
  
 15. PLEASE REVIEW ELEVATOR LOBBY REQUIREMENTS.
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF