| 2009-10-07 17:23:01 | |
| | 1. CONSTRUCTION, DEMOLITION AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 2. SUITABLE EXITS ARE TO BE PROVIDED DURING |
| | CONSTRUCTION. |
| | |
| | 3. TRASH AND DEBRIS SHALL BE REMOVED DAILY. |
| | |
| | 4. WHENEVER A REQUIRED FIRE SAFETY SYSTEM IS OUT OF |
| | SERVICE MORE THAN FOUR (4) HOURS IN A TWENTY FOUR (24) |
| | HOUR PERIOD A FIRE WATCH IS REQUIRED OR THE BUILDING |
| | MUST BE EVACUATED. ALL FIRE WATCH REQUESTS MUST BE IN |
| | WRITING TO THE BATTALION CHIEF OF FIRE PREVENTION OR |
| | THE ASSISTANT FIRE MARSHAL. |
| | |
| | 5. ALL NEW FIRE DAMPERS AFTER INSTALLATION SHALL BE |
| | DROP TESTED TO ENSURE PROPER OPERATION. |
| | |
| | 6. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER REMODEL. |
| | |
| | 7. SEPARATE PLANS AND PERMITS FOR FIRE ALARM SYSTEM |
| | REMODEL. |
| | |
| | 8. ALL NEW ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE |
| | NATIONAL ELECTRICAL CODE. |
| | |
| | 9. NEW SOFFITS SHALL NOT INTERFERE WITH ANY FIRE |
| | SPRINKLER HEAD OPERATION.. |
| | |
| | 10. IS THERE ANY EXISTING SMOKE DETECTOR ABOVE THE FIRE |
| | ALARM CONTROL PANEL. |
| | |
| | 11. ARE ELEVATOR WARNING SIGNS PROVIDED WITHIN THE |
| | ELEVATOR LOBBIES. |
| | |
| | 12. NO FIRE STOPPING DETAILS PROVIDED. |
| | |
| | 13. PLEASE DECLARE ON THE PLANS THAT THE BUILDING IS A |
| | HIGH-RISE BUILDING. |
| | |
| | 14. PLEASE INDICATE NEW CEILING TILE FLAMESPREAD. |
| | |
| | 15. PLEASE REVIEW ELEVATOR LOBBY REQUIREMENTS. |
| | |
| | DENIED |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | WEST PALM BEACH FIRE RESCUE |
| | BUREAU OF FIRE PREVENTION |