| 2009-10-10 13:00:49 | |
| | ** DENIED ** |
| | |
| | |
| | 1) NOTE: PRELIMINARY PLANS AND PERMIT APPLICATIONS WERE |
| | SUBMITTED FOR REVIEW BEFORE 400 AND 450 AUSTRALIAN AVE |
| | WERE GOING TO BE SPLIT. |
| | ALL OF THE PERMITS FOR NEW FIRE LINE, FIRE PUMP, |
| | ELECTRICAL ETC HAVE EITHER BEEN VOIDED OR EXPIRED. |
| | BUILDINGS HAVE NOW BEEN SEPARATED WITHOUT MEETING |
| | MINIMUMS FOR LIFE SAFETY AND FIRE HAZARDS. |
| | THIS INFORMATION WILL BE GIVEN TO FIRE MARSHAL, |
| | BUILDING OFFICIAL, ZONING AND CITY ATTORNEY'S OFFICE. |
| | |
| | MINIMUM CODE COMPLIANCE FOR LIFE SAFETY AND FIRE |
| | HAZARDS NEED TO BE ADDRESSED. |
| | PLEASE SEE NFPA- 70 695, NFPA-20 2003 EDITION, 2005 |
| | NFPA-110 AT A MINIMUM. |
| | |
| | |
| | 2) NOTE: NO LICENSED CONTRACTOR HAS YET APPLIED FOR |
| | PERMIT. PERMIT WAS APPLIED FOR UNDER TBD, TO BE |
| | DETERMINED. |
| | |
| | 3) NOTE: PLEASE OBTAIN IN WRITING FROM THE BUILDING |
| | OWNER/REPRESENTATIVE THAT THE BUILDING SHALL NOT BE |
| | OCCUPIED UNDER GENERATOR POWER. |
| | PLEASE SEE FBC 1006.1.2, NFPA-101 7.8.1.3,7.9.1.1,.1.2 |
| | FOR REQUIRED BATTERY BACK UP FIXTURES REQUIRED. |
| | BASED ON PLANS THERE ARE AREAS WHICH WOULD BE LEFT IN |
| | TOTAL DARKNESS UPON THE TURNING OFF OF A BREAKER, |
| | TRIPPING OF A SINGLE DEVICE. |
| | PLEASE SEE 7.8.1.2.2 FOR ANY DEVICES CONTROLLING |
| | REQUIRED EGRESS LIGHTING AS THEY ARE REQUIRED TO BE |
| | *FAIL-SAFE ON*. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |