| 2009-10-08 20:03:51 | |
| | ** DENIED PLANS ** |
| | |
| | * ELECTRICAL PERMIT IS BEING APPLIED FOR YET NO |
| | ELECTRICAL PLANS/ DETAILS ARE BEING SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SUBMIT ELECTRICAL PLANS SHOWING SCOPE |
| | OF WORK MEETING MINIMUM ELECTRICAL CODE COMPLIANCE WITH |
| | THE 2005 NEC. ( NFPA-70). |
| | PLANS INDICATE SOME NEW PARTITIONS ETC HOWEVER NO |
| | ELECTRICAL IS SHOWN. |
| | PLEASE SEE 210.52 FOR RECEPTACLE SPACE FOR WALLS. |
| | PLEASE SEE 210.52B1 FOR MINIMUM SMALL APPLIANCE |
| | CIRCUITS. |
| | PLEASE SEE 210.52C1-5 FOR COUNTER SPACE RECEPTACLES |
| | REQUIRED IN KITCHEN AND SEE 210.8A6 FOR GFI PROTECTION. |
| | PLEASE SEE 210.12 FOR REQUIRED ARC FAULT PROTECTION. |
| | PLEASE SEE 210.52D FOR REQUIRED BATHROOM RECEPTACLES. |
| | PLEASE SEE 210.11C3 FOR THE BATH CIRCUITS. |
| | PLEASE SEE 210.70 FOR LIGHTING AND CONTROL DEVICES. |
| | ETC. |
| | |
| | 2) NOTE: PLEASE SEE R313.1.2 FOR SMOKE ALARMS WHICH ARE |
| | REQUIRED TO MEET CURRENT NFPA-72 CODES. 11.5.1,11.8.3. |
| | PLEASE SHOW LAYOUT OF EXISTING OR NEW MEETING CURRENT |
| | CODES. |
| | |
| | ** IT IS IMPORTANT TO KNOW THAT AS NO ELECTRICAL IS |
| | SHOWN OR SUBMITTED FOR REVIEW THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE FOLLOWING REVIEW AS MINIMUMS CAN |
| | NOT BE REVIEWED AT THIS TIME. |
| | |
| | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |