| 2009-09-24 08:20:32 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PROVIDE MOTORIZED DAMPER(S) WITH SHUTOFF DAMPER |
| | CONTROLS FOR OUTSIDE AIR INTAKES IN ACCORDANCE WITH |
| | FBC-B 13-409.AB.3.3. |
| | |
| | 2. RETURN AIR TRANSFER DUCT FROM STOCK ROOM IS TOO |
| | SMALL TO MEET EXCEPTIONS UNDER FBC-M 601.4. DESIGN AND |
| | SIZE TRANSFER DUCT TO MEET THE EXCEPTIONS UNDER THIS |
| | SECTION OR A FIELD TEST WILL BE REQUIRED AT FINAL |
| | INSPECTION TO DETERMINE COMPLIANCE WITH THE PRESSURE |
| | DIFFERENTIAL REQUIREMENTS OF THIS SECTION. |
| | |
| | 3. PROVIDE PRODUCT APPROVAL FOR PROPOSED ROOFTOP A/C |
| | STAND WITH CORRESPONDING INSTALLATION INSTRUCTIONS IN |
| | ACCORDANCE WITH FBC-M 304.1 AND FBC-B 106.3.3. |
| | |
| | 4. DUCTS ON PAGE M2 ARE SHADED TO THE POINT THAT THE |
| | SIZES SHOWN ON PLAN ARE ILLEGIBLE. PROVIDE A DUCT |
| | LAYOUT PLAN WITH CLEARLY LEGIBLE DUCT SIZES IN |
| | ACCORDANCE WITH FBC-M 603.1 AND FBC-B 106.1.1. |
| | |
| | 5. PROPOSED CONDENSER LOCATION ON ROOF IS LESS THAN 10' |
| | FROM ROOF EDGE. GUARDS SHALL BE PROVIDED WHERE |
| | APPLIANCES THAT REQUIRE SERVICE ARE LOCATED WITHIN 10 |
| | FEET OF THE ROOF EDGE IN ACCORDANCE WITH FBC-M 304.10. |
| | THE GUARD SHALL EXTEND NOT LESS THAN 30 INCHES BEYOND |
| | EACH END OF THE APPLIANCES AND THE TOP OF THE GUARD |
| | SHALL BE LOCATED NOT LESS THAN 42 INCHES ABOVE THE |
| | ELEVATED SURFACE ADJACENT TO THE GUARD. THE GUARD SHALL |
| | BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| | 21-INCH-DIAMETER SPHERE AND SHALL COMPLY WITH THE |
| | LOADING REQUIREMENTS FOR GUARDS SPECIFIED IN THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 6. SHOW LOCATION OF TOILET ROOM EXHAUST ROOF CAP IN |
| | ACCORDANCE WITH FBC-M 401.4 AND FBC-B 106.1.1. |
| | |