| 2009-10-09 19:12:04 | |
| | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE FAC 69A-3.012 AS THE NFPA-30 NOTED |
| | ON PLANS SHOULD BE THE 2003 EDITION. PLEASE SEE FBC |
| | 2007 W/2009 REVISIONS ALONG WITH FAC 69A-3.012 ETC AS |
| | THE CURRENT EDITION OF THE NEC IS THE 2005 EDITION. ALL |
| | PERMIT APPLICATIONS AFTER DECEMBER 8TH, 2006 AND UP TOT |
| | OCT 1ST 2009 ARE UNDER THE 2005 NFPA-70. |
| | STATING LATEST EDITION ON PLANS IS NOT PERMITTED AS THE |
| | LATEST EDITION COULD PLACE PROJECT INTO ANOTHER CODE. |
| | |
| | 2) NOTE: PLEASE SHOW ALL CLASS AND DIVISION LOCATIONS |
| | ON PLANS AND WIRING METHODS PER NEC 514.3. PLEASE SEE |
| | THE NEC HANDBOOK AS SEVERAL FIGURES AND DETAILS ARE |
| | PROVIDED FOR REFERENCE AND MINIMUMS. |
| | PLEASE SHOW TYPICAL DETAILS FOR SEAL-OFFS AND WIRING |
| | METHOD DETAILS. 514.8 |
| | PLEASE SHOW LOCATION OF NEW OR EXISTING EMERGENCY |
| | DISCONNECTS PER 514.11A, B AND C. |
| | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | 3) NOTE: CONDUCTORS, OVER CURRENT PROTECTION SIZES |
| | COORDINATING WITH PUMP DETAILS NEEDS TO BE ON PLANS. |
| | PLEASE SEE 310.16,240.4 AND 408.4 FOR PANEL SCHEDULE. |
| | |
| | ** FBC ADMINISTRATIVE SECTION FRO ADDITIONAL |
| | INFORMATION ON PLANS TO SHOW MINIMUM CODE COMPLIANCE. |
| | 106.1.1,106.1.2, 106.3.5.1.2 AS ADOPTED BY THE CITY OF |
| | WEST PALM BEACH |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |