| Plan Review Notes For Permit 09090397 |
| Permit Number |
09090397 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-17 17:05:01 | RE-ROOF BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- NOA 03-0501.02 FOR WOOD DECKS AND NOA 03-0501.03 FOR | | | LWC DECKS SUBMITTED ARE EXPIRED. NEED TO PROVIDE | | | CURRENT NOA'S. | | | | | | 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7. | | | | | | ***NOTE: IF GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED REQUIRE SIGNED AND SEALED RAS 117 | | | CALCULATIONS, THEN PROVIDE ORIGINAL SIGNED AND SEALED | | | CALCULATIONS. | | | ALSO, DESIGN PROFESSIONAL DOING THE CALCULATIONS TO | | | VERIFY IF BUILDING IS LOCATED ON EXPOSURE "C". SEE SEC. | | | 1609..4.3 OF 2009 REVISIONS TO THE 2007 FBC. | | | | | | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED | | | BY SEC. 713.13 FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|