| Plan Review Notes For Permit 09090340 |
| Permit Number |
09090340 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-16 14:41:59 | RE-ROOF BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- ENGINEER RESPONSIBLE FOR THE ROOF PROJECT | | | SPECIFICATIONS TO PROVIDE ORIGINAL FLORIDA SEAL, | | | SIGNATURE AND FLORIDA LICENSE NUMBER AS REQUIRED BY | | | SEC. 61G15-23.001 AND 61G15-23.002 OF FLORIDA | | | ADMINISTRATIVE CODE AND BY CHAPTER 471 FLORIDA STATUTE. | | | | | | 2- FLAT ROOF PRODUCT APPROVAL: | | | A) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 ON SHEET 20 OF NOA 07-0228.07 SUBMITTED. | | | | | | B) RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. | | | | | | C) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS | | | TO TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009 | | | REVISIONS TO 2007 FBC, THIS BUILDING IS LOCATED ON | | | EXPOSURE "C". TAKE THIS INTO CONSIDERATION WHEN DOING | | | THE RAS 117 CALCULATIONS. | | | | | | 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | | | | 4- ALL LIGHTNING PROTECTION WORK NEEDS TO BE DONE BY | | | CONTRACTOR WHOSE SCOPE OF WORK INCLUDES THIS TYPE OF | | | WORK. APPLY FOR SEPARATE PERMIT. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|