Plan Review Notes
Plan Review Notes For Permit 09090340
Permit Number 09090340
Review Stop B
Sequence Number 1
Notes
Date Text
2009-09-16 14:41:59RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ENGINEER RESPONSIBLE FOR THE ROOF PROJECT
 SPECIFICATIONS TO PROVIDE ORIGINAL FLORIDA SEAL,
 SIGNATURE AND FLORIDA LICENSE NUMBER AS REQUIRED BY
 SEC. 61G15-23.001 AND 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE AND BY CHAPTER 471 FLORIDA STATUTE.
  
 2- FLAT ROOF PRODUCT APPROVAL:
 A) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON SHEET 20 OF NOA 07-0228.07 SUBMITTED.
  
 B) RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
  
 C) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009
 REVISIONS TO 2007 FBC, THIS BUILDING IS LOCATED ON
 EXPOSURE "C". TAKE THIS INTO CONSIDERATION WHEN DOING
 THE RAS 117 CALCULATIONS.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 4- ALL LIGHTNING PROTECTION WORK NEEDS TO BE DONE BY
 CONTRACTOR WHOSE SCOPE OF WORK INCLUDES THIS TYPE OF
 WORK. APPLY FOR SEPARATE PERMIT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712