| Date |
Text |
| 2009-10-08 15:46:01 | ** DENIED** |
| | |
| | |
| | 1) NOTE: PERMIT APPLICATION STATES TO BUILD A NEW |
| | DETACHED GARAGE HOWEVER THE PLANS ALSO INCLUDE A |
| | REMODEL AND ADDITION TO THE EXISTING DWELLING INCLUDING |
| | NEW BEDROOM. WHAT IS THE ACTUAL SCOPE OF WORK? |
| | THIS AFFECTS THE REVIEW BEING DONE FOR MINIMUM CODE |
| | COMPLIANCE. |
| | PLEASE DESCRIBE PROJECT AND APPLIED SCOPE OF WORK. SEE |
| | NOTES BELOW AS SCOPE OF WORK FOR ELECTRICAL IS ALSO IN |
| | QUESTION. |
| | 105.1, 106.1.1, 106.5 FOR CLARITY OF RECORD PLANS AND |
| | APPLIED SCOPE OF WORK |
| | |
| | 2) NOTE: PLEASE BE SURE THE FOLLOWING MINIMUM CODES ARE |
| | PLACED ON PLANS FOR MINIMUM DESIGN. |
| | 2007 FBC W/ 2009 REVISIONS |
| | 2002 NFPA-72 |
| | 2005 NFPA-70 |
| | |
| | ** REQUIRED MINIMUMS. STATING THE NATIONAL ELECTRICAL |
| | CODE COULD MEAN SEVERAL CODE EDITIONS. |
| | |
| | 3) NOTE: PLEASE PROVIDE A LAYOUT OF THE EXISTING |
| | DWELLING SHOWING NEW OR EXISTING SMOKE ALARMS MEETING |
| | CURRENT NFPA-72 CODES. |
| | PLEASE SEE R313.1.2 AS THIS REQUIRES SMOKE ALARMS TO BE |
| | BROUGHT UP TO CODE. |
| | PLEASE SEE NFPA-72 11.5.1, 11.8.3 FOR CURRENT |
| | REQUIREMENTS INSIDE AND OUTSIDE ALL SLEEPING ROOMS ETC. |
| | |
| | 4) NOTE: THE ELECTRICAL PLANS CONTAINS A NOTE FOR THE |
| | RISER WHICH STATES TO *REMOVE AND UPGRADE* EXISTING |
| | SERVICE YET NO NEW INFORMATION IS SHOWN FOR NEW |
| | SERVICE, NEW AIC RATINGS, NEW SERVICE CONDUCTORS, |
| | MAINS, NO OVER CURRENT PROTECTION FOR SUB PANEL ETC. |
| | CODE COMPLIANCE FOR MANY ITEMS CAN NOT BE REVIEWED IF |
| | INFORMATION IS NOT SUBMITTED SHOWING MINIMUM. |
| | PLEASE SEE 230.70, 230.71, 310.16,240.4,110.9, 215.5 |
| | ETC |
| | |
| | 5) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR SERVICE |
| | PER NEC 220 |
| | |
| | 6) NOTE: PLEASE SEE 250.32 AND 250.50 FOR GROUNDING |
| | ELECTRODE SYSTEM AT DETACHED GARAGE. |
| | |
| | 7) NOTE: BATH CIRCUIT(S) PER 210.11C3 |
| | |
| | 8) NOTE: ARC FAULT PROTECTION PER 210.12 |
| | |
| | ** PLEASE KNOW THAT AS THERE IS INFORMATION NOT YET |
| | SHOWN FOR MINIMUM CODE COMPLIANCE THERE MAY BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| | AT THIS TIME. |
| | |
| | |
| | |
| | |
| | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |