Plan Review Notes
Plan Review Notes For Permit 09090338
Permit Number 09090338
Review Stop E
Sequence Number 1
Notes
Date Text
2009-10-08 15:46:01** DENIED**
  
  
 1) NOTE: PERMIT APPLICATION STATES TO BUILD A NEW
 DETACHED GARAGE HOWEVER THE PLANS ALSO INCLUDE A
 REMODEL AND ADDITION TO THE EXISTING DWELLING INCLUDING
 NEW BEDROOM. WHAT IS THE ACTUAL SCOPE OF WORK?
 THIS AFFECTS THE REVIEW BEING DONE FOR MINIMUM CODE
 COMPLIANCE.
 PLEASE DESCRIBE PROJECT AND APPLIED SCOPE OF WORK. SEE
 NOTES BELOW AS SCOPE OF WORK FOR ELECTRICAL IS ALSO IN
 QUESTION.
 105.1, 106.1.1, 106.5 FOR CLARITY OF RECORD PLANS AND
 APPLIED SCOPE OF WORK
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING MINIMUM CODES ARE
 PLACED ON PLANS FOR MINIMUM DESIGN.
 2007 FBC W/ 2009 REVISIONS
 2002 NFPA-72
 2005 NFPA-70
  
 ** REQUIRED MINIMUMS. STATING THE NATIONAL ELECTRICAL
 CODE COULD MEAN SEVERAL CODE EDITIONS.
  
 3) NOTE: PLEASE PROVIDE A LAYOUT OF THE EXISTING
 DWELLING SHOWING NEW OR EXISTING SMOKE ALARMS MEETING
 CURRENT NFPA-72 CODES.
 PLEASE SEE R313.1.2 AS THIS REQUIRES SMOKE ALARMS TO BE
 BROUGHT UP TO CODE.
 PLEASE SEE NFPA-72 11.5.1, 11.8.3 FOR CURRENT
 REQUIREMENTS INSIDE AND OUTSIDE ALL SLEEPING ROOMS ETC.
  
 4) NOTE: THE ELECTRICAL PLANS CONTAINS A NOTE FOR THE
 RISER WHICH STATES TO *REMOVE AND UPGRADE* EXISTING
 SERVICE YET NO NEW INFORMATION IS SHOWN FOR NEW
 SERVICE, NEW AIC RATINGS, NEW SERVICE CONDUCTORS,
 MAINS, NO OVER CURRENT PROTECTION FOR SUB PANEL ETC.
 CODE COMPLIANCE FOR MANY ITEMS CAN NOT BE REVIEWED IF
 INFORMATION IS NOT SUBMITTED SHOWING MINIMUM.
 PLEASE SEE 230.70, 230.71, 310.16,240.4,110.9, 215.5
 ETC
  
 5) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR SERVICE
 PER NEC 220
  
 6) NOTE: PLEASE SEE 250.32 AND 250.50 FOR GROUNDING
 ELECTRODE SYSTEM AT DETACHED GARAGE.
  
 7) NOTE: BATH CIRCUIT(S) PER 210.11C3
  
 8) NOTE: ARC FAULT PROTECTION PER 210.12
  
 ** PLEASE KNOW THAT AS THERE IS INFORMATION NOT YET
 SHOWN FOR MINIMUM CODE COMPLIANCE THERE MAY BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
  
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  