| 2009-12-17 13:53:21 | *****PARTIAL APPROVAL***** |
| | |
| | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE |
| | BEEN ADDRESSED AS FOLLOWS: |
| | |
| | |
| | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 |
| | EDITION. ON SHEET LS-1, RED-LINE TO 241 INSTEAD OF 214 |
| | |
| | 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE |
| | REFERENCED. ON SHEET LS-1 |
| | |
| | 3. PROVIDE OCCUPANT LOAD CHARACTERISTIC OF THE USE OF |
| | THE SPACE OF DETERMINED AS THE MAXIMUM PROABLE |
| | POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER |
| | IS GREATER. ON SHEET LS-1 |
| | |
| | 4. SPECIFY INTERIOR FINISH FOR WALLS AND CEILINGS IN |
| | TERMRS OF CLASS A, CLASS B, OR CLASS C. ON SHEET LS-1 |
| | |
| | 5. SHOW THE LOCATION OF THE SMOKE ALARMS WHICH SHALL BE |
| | INSTALLED OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. PLEASE BE ADVISED THAT SMOKE |
| | ALARMS, WITH BATTERY BACK-UP, SHALL RECEIVE THEIR |
| | OPERATING POWER FROM THE BUILDING ELECTRICAL SYSTEM. ON |
| | SHEET A-1 & E-1 |
| | |
| | 6. SHOW LOCATION OF THE 2A:10BC RATED FIRE |
| | EXTINGUISHER(S). THIS MAY BE ACCOMPLISHED BY EITHER ONE |
| | OF THE FOLLOWING: 1) PROVIDE ONE FIRE EXTINGUISHER ON |
| | THE OUTSIDE COMMON TO ALL THREE DWELLING UNITS OR 2) |
| | PROVIDE ONE EXTINGUISHER INSIDE EACH DWELLING UNIT. ON |
| | SHEET LS-1 |
| | |
| | 7. VERIFY THAT THE NUMERICAL ADDRESS FOR THE BUILDING |
| | (AT LEAST 6" IN HEIGHT AND 1" IN WIDTH) IS VISIBLE FROM |
| | 5TH STREET. IN ADDITION EACH DWELLING UNIT DESIGNATION |
| | (AT LEAST 3" IN HEIGHT AND 1" IN WIDTH) IS POSTED. |
| | UNDERSTOOD BY CONTRACTOR |
| | |
| | PLEASE BE ADVISED HOWEVER THAT ONLY ONE SET OF PLANS |
| | HAVE BEEN SUBMITTED; PLANS HEETS A-1, LS-1, AND E-1 TO |
| | BE FIRE-STAMPED WHEN AN ADDITIONAL, NO MORE THAN TWO |
| | ADDITIONAL, PLAN SET HAS BEEN SUBMITTED. |
| | |