Plan Review Notes
Plan Review Notes For Permit 09090334
Permit Number 09090334
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-10-26 12:36:56*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. PROVIDE OCCUPANT LOAD CHARACTERISTIC OF THE USE OF
 THE SPACE OF DETERMINED AS THE MAXIMUM PROABLE
 POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER
 IS GREATER.
  
 4. SPECIFY INTERIOR FINISH FOR WALLS AND CEILINGS IN
 TERMRS OF CLASS A, CLASS B, OR CLASS C.
  
 5. SHOW THE LOCATION OF THE SMOKE ALARMS WHICH SHALL BE
 INSTALLED OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS. PLEASE BE ADVISED THAT SMOKE
 ALARMS, WITH BATTERY BACK-UP, SHALL RECEIVE THEIR
 OPERATING POWER FROM THE BUILDING ELECTRICAL SYSTEM.
  
 6. SHOW LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S). THIS MAY BE ACCOMPLISHED BY EITHER ONE
 OF THE FOLLOWING: 1) PROVIDE ONE FIRE EXTINGUISHER ON
 THE OUTSIDE COMMON TO ALL THREE DWELLING UNITS OR 2)
 PROVIDE ONE EXTINGUISHER INSIDE EACH DWELLING UNIT.
  
 7. VERIFY THAT THE NUMERICAL ADDRESS FOR THE BUILDING
 (AT LEAST 6" IN HEIGHT AND 1" IN WIDTH) IS VISIBLE FROM
 5TH STREET. IN ADDITION EACH DWELLING UNIT DESIGNATION
 (AT LEAST 3" IN HEIGHT AND 1" IN WIDTH) IS POSTED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722