| Plan Review Notes For Permit 09090334 |
| Permit Number |
09090334 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-10-26 12:36:56 | *****DENIED***** | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | | REFERENCED. | | | | | | 3. PROVIDE OCCUPANT LOAD CHARACTERISTIC OF THE USE OF | | | THE SPACE OF DETERMINED AS THE MAXIMUM PROABLE | | | POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER | | | IS GREATER. | | | | | | 4. SPECIFY INTERIOR FINISH FOR WALLS AND CEILINGS IN | | | TERMRS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 5. SHOW THE LOCATION OF THE SMOKE ALARMS WHICH SHALL BE | | | INSTALLED OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE | | | VICINITY OF THE BEDROOMS. PLEASE BE ADVISED THAT SMOKE | | | ALARMS, WITH BATTERY BACK-UP, SHALL RECEIVE THEIR | | | OPERATING POWER FROM THE BUILDING ELECTRICAL SYSTEM. | | | | | | 6. SHOW LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S). THIS MAY BE ACCOMPLISHED BY EITHER ONE | | | OF THE FOLLOWING: 1) PROVIDE ONE FIRE EXTINGUISHER ON | | | THE OUTSIDE COMMON TO ALL THREE DWELLING UNITS OR 2) | | | PROVIDE ONE EXTINGUISHER INSIDE EACH DWELLING UNIT. | | | | | | 7. VERIFY THAT THE NUMERICAL ADDRESS FOR THE BUILDING | | | (AT LEAST 6" IN HEIGHT AND 1" IN WIDTH) IS VISIBLE FROM | | | 5TH STREET. IN ADDITION EACH DWELLING UNIT DESIGNATION | | | (AT LEAST 3" IN HEIGHT AND 1" IN WIDTH) IS POSTED | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|