| Plan Review Notes For Permit 09090324 |
| Permit Number |
09090324 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-11-18 12:57:16 | PROVISO | | | REVISION REQUIRED TO CORRECT THE FOLLOWING. | | | | | | 1) REMOVE EQUIPMENT GROUND FROM METER TO DISCONNECT. | | | 250.24(A) (5). | | | | | | 2} GROUNDING ELECTRODE MUST BE A #4. 250.66 | | | | | | 3} HVAC CALCULATION INCORRECT IN THE LOAD CALCULATION. | | | 220.82 AND OR 220.83. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|