| Plan Review Notes For Permit 09090299 |
| Permit Number |
09090299 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-16 11:00:09 | ****PROVISO - REVISION REQUIRED**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE (FOR | | | SHUTTERS) OR PROVIDE ALL INFORMATION TO SHOW CODE | | | COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301, | | | FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN | | | THE LOBBY OR ON THE INTERNET AT | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | | INSTALLATION.PDF | | | | | | 2. PROVIDE A FLOOR PLAN SHOWING LOCATION OF PROPOSED | | | DOOR, WINDOWS, AND SHUTTERS. | | | | | | 3. SHOW COMPLIANCE FOR BEDROOMS, EMERGENCY EGRESS, FBC | | | R303. | | | | | | 4. SHOW LOCATION AND SCOPE (APPROX SQUARE FEET) OF | | | DRYWALL REPAIR AREA. | | | | | | 4. SUBMIT ITEMS 1 - 4 AS A REVISION BEFORE FIRST | | | INSPECTION. | | | | | | | | | | | | | | | |
|