2010-01-13 17:10:04REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED
  
 1. OK
  
 2. DESIGNER'S RESPONSE INDICATES EXTERIOR DUCTWORK IS
 TO BE CONSTRUCTED OF FIBER REINFORCED PLASTIC. EXTERIOR
 DUCTWORK SHALL BE DESIGNED AND INSTALLED FOR WIND
 RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. PROVIDE
 DUCT MANUFACTURER'S DATA DEMONSTRATING THE WIND
 RESISTANCE CAPABILITIES OF THE PROPOSED EXTERIOR
 DUCTWORK.
  
 3. NO INFORMATION WAS PROVIDED REGARDING THE WIND
 RESISTANCE CAPABILITIES OF THE OUTDOOR PACKAGE UNIT.
 SCREEN WALLS DO NOT ELIMINATE THE FACT THAT THE UNIT IS
 EXPOSED TO WIND AND SUBJECT TO WIND PRESSURES IN A HIGH
 WIND EVENT. THE EXHAUST FAN MUST ALSO BE DESIGNED FOR
 WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12.
 PROVIDE SUPPORTING DOCUMENTATION WHICH DEMONSTRATES
 COMPLIANCE.
  
 4. OK
  
 NOTE: PAGE G-00-05 DECLARES THIS AS A CATEGORY IV
 STRUCTURE, WITH EXPOSURE CATEGORY OF C AND A WIND
 IMPORTANCE FACTOR OF 1.15. WHEN PROVIDING WIND
 RESISTANCE DATA FOR THE MECHANICAL EQUIPMENT AND
 APPLIANCES ABOVE, THESE FACTORS SHALL BE TAKEN INTO
 ACCOUNT.
  