| 2009-09-29 15:06:37 | REVIEW #: 1ST **PLAN REVIEW ONLY** |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PAGE M-02-02: FLOOR PLAN SHOWS LESS THAN 3 FEET |
| | BETWEEN ACU 201 AND THE NORTH WALL OF THE ENCLOSURE. |
| | MANUFACTURER'S DATA REQUIRES A MINIMUM OF 60 INCHES |
| | CLEARANCE AT THIS LOCATION. PLEASE SHOW HOW PROPER |
| | ACCESS FOR SERVICE AND MAINTENANCE OF THE APPLIANCE. |
| | CLEARANCES AROUND APPLIANCES TO ELEMENTS OF PERMANENT |
| | CONSTRUCTION, INCLUDING OTHER INSTALLED EQUIPMENT AND |
| | APPLIANCES, SHALL BE SUFFICIENT TO ALLOW INSPECTION, |
| | SERVICE, REPAIR OR REPLACEMENT WITHOUT REMOVING SUCH |
| | ELEMENTS OF PERMANENT CONSTRUCTION IN ACCORDANCE WITH |
| | FBC-M 306.1 AND IN ACCORDANCE WITH THE MANUFACTURER'S |
| | INSTRUCTIONS PER FBC-M 304.1. |
| | |
| | 2. PAGE M-02-02: FLOOR PLAN REFERENCES STRUCTURAL DETAL |
| | FOR WALL AND ROOF SUPPORT OF EXTERIOR DUCTS. NO SUCH |
| | DETAIL WAS PROVIDED IN THESE PLANS. PROVIDE STRUCTURAL |
| | DETAIL DESIGNED FOR WIND RESISTANT DESIGN AND |
| | INSTALLATION OF EXTERIOR DUCTWORK IN ACCORDANCE WITH |
| | FBC-M 301.12. |
| | |
| | 3. PROVIDE MANUFACTURER'S WIND RESISTANCE DATA FOR ALL |
| | OUTDOOR APPLIANCES EXPOSED TO WIND, SUCH AS ACU-201 AND |
| | EF-201 AS WELL AS DETAILS FOR INSTALLATION AND |
| | ATTACHMENT TO STRUCTURE FOR WIND RESISTANCE IN |
| | ACCORDANCE WITH FBC-M 301.12. |
| | |
| | 4. EF-201 APPEARS TO BE ON A ROOF AT A HEIGHT EXCEEDING |
| | 16 FEET ABOVE GRADE. WHERE APPLIANCES REQUIRING ACCESS |
| | ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A |
| | HEIGHT EXCEEDING 16 FEET, SUCH ACCESS SHALL BE PROVIDED |
| | BY A PERMANENT APPROVED MEANS OF ACCESS, THE EXTENT OF |
| | WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO THE |
| | EQUIPMENT AND APPLIANCES' LEVEL SERVICE SPACE IN |
| | ACCORDANCE WITH FBC-M 306.5. SUCH ACCESS SHALL NOT |
| | REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 |
| | INCHES HIGH OR WALKING ON ROOFS HAVING A SLOPE GREATER |
| | THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |