Plan Review Notes
Plan Review Notes For Permit 09090230
Permit Number 09090230
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-09-30 15:46:011009 BANYAN BOULEVARD
  
 1. ENSURE THAT FIRE AND PARAMEDICAL ACCESS IS
 MAINTAINED DURING WORK ACTIVITIES.
  
 2. ANY CUTTING OR WELDING OPERATIONS SHALL COMPLY WITH
 NFPA 51B.
  
 3. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 4. ALL STORAGE TANKS ARE TO BE PROPERLY LABELED.
 CONTROL VALVES ARE TO BE LABELED TO ENSURE RAPID
 CLOSURE IN THE EVENT OF AN EMERGENCY.
  
 5. ALL ELECTRICAL WORK SHALL COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM EQUIPMENT.
  
 7. DUCT SMOKE DETECTOR SHOWN ON PAGE M-02-02 WILL BE
 CONNECTED TO WHAT FIRE ALARM EQUIPMENT. NEW OR
 EXISTING.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
  