| Plan Review Notes For Permit 09090230 |
| Permit Number |
09090230 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-10-05 07:40:54 | PASSED WITH PROVIOS: | | | DEAN LAUDERMILK, PROJECT COORDINATOR, | | | OFFICE 494-1083, EMAIL [email protected] | | | SHEET CU-01-03: | | | 1. LOCATION - THROUGH-OUT SHEET: CTN???S (2 AND 3??? | | | PVC) SHOWN ARE NOT DEFINED ON SHEET G-00-02. WHAT ARE | | | THEY? SAME COMMENT HOLDS TRUE ON SHEET CU-01-03. | | | 2. LOCATION - C-4: WHERE IS THE WATER METER AT THE | | | BACKFLOW PREVENTER? ALL PRODUCTION WATER IS SUPPOSED TO | | | BE MONITORED. THE METER DOES NOT SHOW UP ON SHEET | | | CD-01-02, DETAIL 7 EITHER. | | | 3. C-4: WHY DOES THE DEDICATED EYE WASH WATER LINE | | | DISAPPEAR INTO THE METER PUMP BUILDING? IT SHOULD HAVE | | | A TEE IN THE LINE INTO THE BUILDING FOR THE EYE WASH | | | STATION INSIDE. | | | SHEET D-02-02: | | | 1. LOCATION ??? A2: THE CHLORINE UNLOADING STATION IS | | | 20??? EAST OF THE GARAGE DOORS INTO THE EXISTING | | | CHLORINE BUILDING. WHY WAS THIS LOCATION CHOSEN? THE | | | PAVEMENT ALSO ENDS AT THE GARAGE DOORS. WHY NOT PLACE | | | THE CHLORINE FILL STATION AT THE GARAGE DOORS SO THERE | | | IS NOT TOO MUCH HOSE REELED OUT. AN EVEN BETTER | | | LOCATION WOULD BE INSIDE THE BUILDING AND HAVE THE FILL | | | STATION INSIDE THE CONTAINMENT STRUCTURE. | | | |
|