2009-10-10 11:15:24 
 ** DENIED **
  
  
 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW
 AND NOT FOR PERMIT UNDER A LICENSED CONTRACTOR. PLANS
 SUBMITTED FOR PERMIT AFTER OCTOBER 1ST, 2009 SHALL BE
 UNDER THE FOLLOWING CODES.
 2008 NFPA-70
 2006 NFPA-101
 2007 FBC W/ SECOND SUPPLEMENTS TO THE 2009 SUPPLEMENTS
  
 2) NOTE: PLEASE SHOW CLASS/DIVISION LOCATIONS PER NEC
 500
  
 3) NOTE: THERE IS A NEW MANUFACTURED CONCRETE BUILDING
 YET NO ELECTRICAL SHOWN FOR THIS BUILDING. PLANS SEEMS
 TO INDICATE EQUIPMENT IN THIS LOCATION.
 PLEASE ALSO SEE 250.50 GROUNDING ELECTRODE SYSTEM
 REQUIRED FOR STRUCTURES CONTAINING ELECTRICAL.
 PLEASE SEE 230.70 230.79 AND 225.31-225.39 FOR FEEDERS
 OR BRANCH CIRCUITS FOR DISCONNECTING MEANS AS WELL AS
 ANY SERVICES.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  