| 2009-10-10 11:15:24 | | | | ** DENIED ** | | | | | | | | | 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW | | | AND NOT FOR PERMIT UNDER A LICENSED CONTRACTOR. PLANS | | | SUBMITTED FOR PERMIT AFTER OCTOBER 1ST, 2009 SHALL BE | | | UNDER THE FOLLOWING CODES. | | | 2008 NFPA-70 | | | 2006 NFPA-101 | | | 2007 FBC W/ SECOND SUPPLEMENTS TO THE 2009 SUPPLEMENTS | | | | | | 2) NOTE: PLEASE SHOW CLASS/DIVISION LOCATIONS PER NEC | | | 500 | | | | | | 3) NOTE: THERE IS A NEW MANUFACTURED CONCRETE BUILDING | | | YET NO ELECTRICAL SHOWN FOR THIS BUILDING. PLANS SEEMS | | | TO INDICATE EQUIPMENT IN THIS LOCATION. | | | PLEASE ALSO SEE 250.50 GROUNDING ELECTRODE SYSTEM | | | REQUIRED FOR STRUCTURES CONTAINING ELECTRICAL. | | | PLEASE SEE 230.70 230.79 AND 225.31-225.39 FOR FEEDERS | | | OR BRANCH CIRCUITS FOR DISCONNECTING MEANS AS WELL AS | | | ANY SERVICES. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|