| 2009-09-30 10:22:13 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 BUILDING |
| | FBC-2007 CHAPTER 1 |
| | FBC-2007 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHTS A-4 & P-2 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES. INDICATE THE TOTAL SQUARE |
| | FOOTAGE BEING DRAINED BY EACH ROOF DRAIN, GUTTER & |
| | DOWNSPOUT. CALCULATIONS SHALL SHOW 1/2 THE AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS AS WELL AS THE AREA |
| | OF A ROOF DRAINING ON TO THE ROOF FROM ABOVE ADDED TO |
| | EACH AREA. THE GUTTER AND DOWNSPOUT SIZE SHALL BE |
| | INDICATED. TABLES 1106.2 & 1106.6. |
| | |
| | 2. ALL SHEETS WITH RUIZ - BRITO TITLE BLOCK SHALL |
| | INCLUDE THE FIRM LICENSE NUMBER PER FAC 61G1-16.004(2) |
| | AND THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT |
| | PER FAC 61G1-16.004(7). FS 481.219 & 481.2055. |
| | |
| | 3. SHTS A-8, P-1 & P-4 INDICATE GAS HEATER & |
| | APPLIANCES. SEE GAS REVIEW FOR SEPARATE GAS |
| | PERMIT/PLANS/REQUIRMENTS. |
| | |
| | 4. SHT P-1 FLOOR DRAINS IN THE MEAT CUTTING/STORAGE |
| | AREAS. THE MAXIMUM DISTANCE FROM THE 3" FLOOR DRAINS TO |
| | THE VENT IS 12 FEET PER TABLE 906.1. THE FLOOR DRAINS |
| | PER THE 1/8TH SCALE ARE INDICATED AS BEING 14 TO 16 |
| | FEET FROM THE VENT. |
| | |
| | 5. SHT P-1 DELI AREA NOTE STATES "8 INCH RWL 4,962 SF", |
| | BUT NO ROOF DRAIN IS SHOWN. PLEASE CLARIFY. SECTION |
| | 106.1.1 & TABLE 1106.3. |
| | |
| | 6. SHTS P-1 & P-3 INDICATE NEW FIXTURES DRAINING INTO |
| | THE EXISTING GREASE INTERCEPTOR. THE GREASE INTERCEPTOR |
| | SHALL BE INSPECTED FOR SIZE AND TO MAKE SURE IT IS |
| | OPERATING PROPERLY. ARTICLE III SECTION 90-124(7). |
| | PLEASE CONTACT HOLLY MCGRATH LABORATORY SUPERVISOR, |
| | PUBLIC UTILITIES DEPARTMENT FOR INSPECTION AND APPROVAL |
| | OF EXISTING GREASE INTERCEPTOR. A WRITTEN DETERMINATION |
| | IS REQUIRED PRIOR TO PERMIT BEING ISSUED. |
| | |
| | 7. SHT P-4 WATER ISOMETRIC. AIR CHAMBERS SHOWN AT EACH |
| | FIXTURE ARE NOT APPROVED. PLEASE DELETE FROM ISOMETRIC. |
| | PDI-WH 201. |
| | |
| | 8. SHT P-5 PLUMBING NOTES # 9. AIR CHAMBERS ARE NOT |
| | APPROVED. PLEASE DELETE FROM NOTE. PDI-WH 201. |
| | |
| | 9. SHT P-5 WATER HEATER DETAIL. THERMAL EXPANSION |
| | CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE |
| | INDICATE METHOD. |
| | |
| | 10. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE |
| | TO THE BUILDING. PLEASE INDICATE IF THERE IS AN |
| | EXISTING RPZV BACKFLOW OR IF A BACKFLOW WILL BE |
| | INSTALLED. SECTION 608.13.2. |
| | |
| | 11. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. |
| | PLEASE SHOW THE LOCATION OF THE REQUIRED DRINKING |
| | FOUNTAIN. ALSO SUBMIT A DETAIL SHOWING COMPLIANCE WITH |
| | SECTION 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION |
| | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING. |
| | |
| | 12. SUBMIT A DETAIL FOR THE TOILET ROOMS SHOWING |
| | COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22 |
| | WITH ALL SUBSECTIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |