| 2009-10-07 14:04:15 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLANS HAVE BEEN SUBMITTED UNDER PERMIT |
| | APPLICATION HOWEVER NO LICENSED CONTRACTOR HAS BEEN |
| | SIGNED ON APPLICATION. ONCE ELECTRICAL REVIEW IS FOUND |
| | TO PASS FOR REVIEW THE REVIEW STATUS WILL STILL REMAIN |
| | IN FAILED STATUS UNTIL SUCH TIME LICENSED CONTRACTOR(S) |
| | HAS BEEN DETERMINED ETC |
| | |
| | 2) NOTE: PLANS ARE NOT SHOWING THE CORRECT ADOPTED |
| | CODES BY THE STATE OF FLORIDA. PLEASE KNOW THAT AS OF |
| | MARCH 1ST, 2009 THE STATE ADOPTED THE FOLLOWING AT A |
| | MINIMUM. |
| | 2007 FBC W/2009 REVISIONS. |
| | AS OF DECEMBER 31ST, 2008 THE STATE ADOPTED UNDER FAC |
| | 69A-3.012 AND 69A-60.004, .003 THE 2006 NFPA-101, 2006 |
| | NFPA-1. ELECTRICAL PLANS INDICATE THE 2003 NFPA-101 |
| | PLANS SUBMITTED BEFORE OCTOBER 1ST 2009 ARE UNDER THE |
| | 2005 NATIONAL ELECTRICAL CODE. ( NFPA-70). |
| | PLEASE BE SURE TO LIST THE FOLLOWING MINIMUM CODES ON |
| | PLANS. |
| | |
| | 2007 FBC W/2009 REVISIONS |
| | 2006 NFPA-101 |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 ( IF APPLICABLE FOR BUILDINGS WITH FIRE |
| | ALARM SYSTEMS) |
| | |
| | ** SOME CODE SECTIONS FOR EXAMPLE ON E-1 NOTE #8 IS |
| | ACTUALLY FROM THE 1996 NEC. THIS CODE SECTION NEEDS TO |
| | BE REVISED TO THE APPLICABLE SECTION FROM THE 2005 NEC. |
| | |
| | 3) NOTE: PLEASE SEE FAC 61G1-60.004 FOR MISSING |
| | REQUIRED INFORMATION IN THE TITLE BLOCKS FOR ARCHITECT |
| | AND ARCHITECTURAL FIRM. |
| | PLEASE SEE FS 481.219 FOR REQUIRED CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | IF THERE ARE ANY QUESTIONS ON LICENSING REQUIRED AND |
| | INFORMATION REQUIRED TO BE LOCATED ON TITLE BLOCKS, |
| | PLEASE CONTACT THE BOARD OF ARCHITECT'S LEGAL COUNSEL. |
| | |
| | 4) NOTE: LANDSCAPE ARCHITECTURAL SHEETS. PLEASE SEE FS |
| | 481.319, 321 FOR REQUIRED LICENSING FOR FIRM, |
| | CORPORATION, PARTNERSHIP ETC. |
| | ** PLEASE KNOW ANY LANDSCAPE LIGHTING/SITE LIGHTING |
| | WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS PER THE |
| | BUILDING OFFICIAL. HOWEVER BASE PLANS FOR ENERGY CODE |
| | COMPLIANCE WILL BE REQUIRED TO SHOW CODE COMPLIANCE. |
| | |
| | |
| | 5) NOTE: NO PLANS, DOCUMENTS OR INFORMATION SUBMITTED |
| | FOR LIGHTING PERFORMANCE CALCULATIONS UNDER FBC CHAPTER |
| | 13 WERE SUBMITTED. PLEASE SEE 13-415.AB.5 FOR INTERIOR |
| | AND 13-415.AB.2.2 FOR EXTERIOR. |
| | ** AS NOT CALCULATIONS MEETING ENERGY CODE WERE |
| | SUBMITTED NO REVIEW OF THESE ITEMS COULD BE DONE. |
| | ** EVEN WHEN A BUILDING DOES NOT MEET THE DEFINITION OF |
| | A RENOVATION, THE MINIMUM PRESCRIPTIVE REQUIREMENTS OF |
| | THE ENERGY CODE STILL MUST BE MET. |
| | |
| | 6) NOTE: PLEASE SEE 13-415.AB.1.1,.1.2, .1.3 AND .1.4 |
| | FOR MINIMUM LIGHTING CONTROLS. BASED ON THE PLANS ITEMS |
| | SUCH AS SINGLE POLE SWITCHES AS SHOWN ON SYMBOL LEGEND |
| | AND PLANS DOES NOT MEET MINIMUM REQUIRED. |
| | *** IT IS IMPORTANT TO SEE SECTIONS NOTED AND TO CALL |
| | TO GO OVER ANY QUESTIONS. |
| | |
| | 7) NOTE: PLANS INDICATE PANEL L IN THE MIDDLE OF THE |
| | STORAGE ROOM WALL. PLEASE RELOCATE AS STORAGE IS NOT |
| | PERMITTED IN THIS AREA. |
| | ALSO KNOW THAT PROTECTION OF ELECTRICAL EQUIPMENT IN |
| | ANY LOCATION WHERE CONTACT OF ROLLING EQUIPMENT/STORAGE |
| | UNITS COULD DAMAGE ELECTRICAL EQUIPMENT WILL BE |
| | REQUIRED. |
| | ** PLEASE VERIFY LOCATION AS THE ENLARGED ELECTRICAL |
| | ROOM PLANS INDICATES THE *L* PANEL ON THE MAIN |
| | ELECTRICAL ROOM YET THE PLANS INDICATE THIS SAME PANEL |
| | IN STORAGE ROOM ON WALL.?? |
| | |
| | 110.26, 110.27B, 408.17, 240.24 ETC. |
| | |
| | 8) NOTE: THE AIC RATINGS FOR ALL EQUIPMENT, PANELS AND |
| | BREAKERS NEED TO BE ON PLANS AT THIS TIME. 110.9 |
| | NOTE MENTIONS TO OBTAIN INFORMATION AND VERIFY HOWEVER |
| | THIS INFORMATION IS READILY AVAILABLE AT THIS TIME. |
| | SOME RATINGS ARE SHOWN FOR PANELS WITH SERIES RATINGS. |
| | |
| | 9) NOTE: PLEASE SEE FBC 13-413.AB.2 FOR REQUIRED NOTES |
| | TO BE PLACED ON PLANS. |
| | |
| | 10) NOTE: PLEASE SEE FBC 13-413.AB.1 FOR REQUIRED WORST |
| | CASE VOLTAGE DROP CALCULATIONS REQUIRED. |
| | |
| | 11) NOTE: COMPLETE LOAD CALCULATIONS WERE NOT |
| | SUBMITTED/SHOWN PER NEC. HOW WERE LOADS DERIVED? |
| | PLEASE SEE 220.12,220.14,220.42,220.44, 220.43 FOR |
| | RECEPTACLES, LIGHTING, TRACK LIGHTING LOADS ETC. |
| | ** PLEASE BE SURE TO SEE 215.3,230.42 ETC FOR ALL |
| | CONTINUOUS LOADS TO BE SHOWN AT 125% INCLUDING LARGEST |
| | MOTOR LOADS. |
| | |
| | 12) NOTE: IN THE MIDDLE OF E-4 THERE IS A PANEL |
| | SCHEDULE FOR A/C EQUIPMENT HOWEVER PANEL IS NOT |
| | IDENTIFIED. ACTUALLY SATES * PANE*. PLEASE ALSO |
| | COORDINATE THE LOCATION IN WHICH THIS PANEL IS FED |
| | FROM. THE *PANE* PANEL SCHEDULE STATES IT IS FED FROM |
| | PANEL DP, YET BASED ON THE RISER THIS IS A PANEL TAPPED |
| | FROM THE MAIN GUTTER AND NOT FED FROM DP. |
| | PLEASE ADJUST AND COORDINATE INFORMATION ON RISER. |
| | 215,220,230,240,408 ETC GIVEN AS GENERAL CHAPTERS FOR |
| | COORDINATION OF ALL INFORMATION. |
| | |
| | 13) NOTE: SIGN CIRCUIT STILL REQUIRED AT FRONT ENTRANCE |
| | PER 600.5 |
| | |
| | 14) NOTE: ANY WINDOW AREAS SHALL HAVE SHOW WINDOW |
| | RECEPTACLES PER 210.62. PLEASE ALSO BE SURE TO ADJUST |
| | LOAD CALCULATIONS PER 220.43, 220.14 |
| | |
| | ** AS THERE IS INFORMATION NOT YET SUBMITTED REQUIRED |
| | FOR MINIMUM CODE COMPLIANCE REVIEW THERE MAY VERY WELL |
| | BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT |
| | BE MADE AT THIS TIME. |
| | |
| | |
| | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |