| 2009-09-28 14:19:37 | BUILDING PLAN REVIEW |
| | PERMIT: 09090218 |
| | ADD: 5011 BROADWAY AV |
| | CONT: TO BE DETERMINED |
| | TEL: (786)368-6455 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE W/ 2009 |
| | SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | SHEET A-1 SITE PLAN NOTES & CODE INFORMATION: |
| | |
| | 1) WRONG ADDITION OF THE CODE. 110.2* W. P. B. |
| | ADMINISTRATIVE CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PERMIT WAS |
| | ISSUED. 2007 FBC W/ 2009 SUPPLEMENTS 2007 EFBC-LEVEL |
| | III SECTION 405 |
| | B) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503, |
| | CHAPTER 6, TABLE 601. PLANS INDICATE BUILDING TYPE IV |
| | WHICH IS HEAVY TIMBER, UNDER THECURRENT CODE.PLANS |
| | DRAWN UNDER THE 2001 FBC THTE EQUIVALENT IV |
| | CLASSIFICATION TO THE 2007 FBC IS NOW A TYPE II-B. |
| | PLEASE NOTE THE MINIMUM STANDARD THAT THIS BUILDING |
| | COULD BE BUILT UNDER THE 2007 FBC PER TABLE 503 IS A |
| | V-B BUILDING FOR MERCANTILE WITH AREA INCREASES FOR |
| | FRONTAGE INCREASE AND 506.2 AND SPRINKLER INCREASE PER |
| | 506.3 |
| | D) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED? |
| | E) WEATHER A SPRINKLER SYSTEM IS REQUIRED? |
| | 2007 EXISTING BLDG CODE 804.2.2 AUTOMATIC FIRE |
| | DETECTION. WHERE REQUIRED BY THE FLORIDA BUILDING CODE, |
| | BUILDING FOR NEW BUILDINGS, AUTOMATIC FIRE DETECTION |
| | SYSTEMS SHALL BE PROVIDED THROUGHOUT THE WORK AREA. |
| | 903.2.6 GROUP M. AN AUTOMATIC SPRINKLER SYSTEM SHALL BE |
| | PROVIDED THROUGHOUT BUILDINGS CONTAINING A GROUP M |
| | OCCUPANCY WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS: |
| | 1. WHERE A GROUP M FIRE AREA EXCEEDS 12,000 SQUARE FEET |
| | (1115 M2). |
| | PLEASE PROVIDE A FIRE SPRINKLER PLAN. |
| | F) IF THIS PERMIT IS TO BE PHASED PLEASE PROVIDE TIME |
| | LINES FOR EACH PHASE, THE BUILDING OFFICIAL MAY REQUIRE |
| | SEPERATE PERMITS DEPENDING ON THE PHASED TIME LINE. |
| | |
| | 2) NOTE PRODUCT APPROVALS ARE NOT REQUIRED AT TIME OF |
| | PERMIT ISSUANCE BUT WILL BE CONSIDERED A REVISION AND A |
| | SEPERATE REVIEW AND ASSOCIATED FEES |
| | WOULD BE REQUIRED. |
| | FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2 |
| | COPIES OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE |
| | AS FOLLOWS: |
| | A) FIXED GLASS/ STORE FRONT |
| | B) EXTERIOR GLAZED SWING DOORS & SIDELITES |
| | C) SINGLE EXTERIOR HOLLOW METAL SWING DOORS |
| | D) PAIRS OF EXTERIOR HOLLOW METAL SWING DOORS |
| | E AUTOMATIC SLIDING DOORS& SIDE LITES |
| | F) TRUSS ANCHORS |
| | G) WALL LOUVERS- DECRATIVE SHUTTERS |
| | H) EFIS WALL SYSTEMS |
| | I) SHUTTERS BAHAMA STYLE- ON TOWERS |
| | J) ROOF ASSEMBLIES UNDERLAYMENT, MODIFIED BITUMEN & |
| | ROOF TILE |
| | |
| | 3A) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. |
| | |
| | 3B) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 4) FLOOR PLAN A-3 INDICATES USE OF POWER HORIZONTAL |
| | SLIDING DOORS. SHOW COMPLIANCE WITH: |
| | 1008.1.3.3 HORIZONTAL SLIDING DOORS. IN OTHER THAN |
| | GROUP H OCCUPANCIES, HORIZONTAL SLIDING DOORS PERMITTED |
| | TO BE A COMPONENT OF A MEANS OF EGRESS IN |
| | ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2 SHALL |
| | COMPLY WITH ALL OF THE FOLLOWING CRITERIA: |
| | 1. THE DOORS SHALL BE POWER OPERATED AND SHALL BE |
| | CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF |
| | POWER FAILURE. |
| | 2. THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD FROM |
| | BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. |
| | 3. THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT |
| | EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND |
| | 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE |
| | MINIMUM REQUIRED WIDTH. |
| | 4. THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO |
| | EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS |
| | (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT |
| | TO THE OPERATING DEVICE. |
| | 5. THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE |
| | FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE |
| | SELF-CLOSING OR AUTOMATIC-CLOSING BY |
| | SMOKE DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH |
| | NFPA 80 AND SHALL COMPLY WITH SECTION 715 . |
| | 6. THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY |
| | POWER SUPPLY. |
| | 7. THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY |
| | SUPERVISED. |
| | |
| | 5A) THE FOLLOWING ITEMS WILL DEAL WITH ROOFING REPORTS |
| | BE ADVISED OF THE INFORMATION THAT WILL NEED TO BE |
| | HIGHLIGHTED BEFORE SUBMITTAL TO THE BUILDING |
| | DEPARTMENT; THIS ROOF IS MISSING OR NOT IN COMPLIANCE |
| | WITH THE FOLLOW ITEMS: |
| | (FLAT ROOF) |
| | ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___ |
| | CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED. |
| | ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE ___ |
| | . |
| | ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD |
| | THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS |
| | DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED FASTENER SPACING, PREPARED |
| | , SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| | SUBMITTED. |
| | ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| | ENHANCED FASTENING ALLOWED. |
| | |
| | 5B) ROOF TILE FOR SLOPED ROOFS, PLEASE INDICATE WHICH |
| | FASTENING SYSTEM SHALL BE USED.106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. MOMENT OF OVERTURNING, 1609.7.3 |
| | RIGID TILE. |
| | |
| | 5C) NO INFORMATION FOR FASTENING OF HIP BOARD OR HIP |
| | TILE. 1507.3.8 APPLICATION. TILE SHALL BE APPLIED |
| | ACCORDING TO THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS OR RECOMMENDATIONS OF THE FRSA/RTI |
| | 07320/08-05 (FOURTH EDITION). |
| | |
| | 6A) A-7 NOR STRUCTURAL PLANS ARE MISSING THE NEW A/C |
| | CURBS, HOW THE WEIGHT WILL BE CARRIED ON THE WOOD |
| | TTRUSS SYSTEM AND BAR JOIST SYSTEM (MEZZANINE LEVEL) , |
| | WHERE THE POINT LOADING WILL NEED TO BE TAKEN IN AFFECT |
| | AND THE PANEL POINTS REINFORCED, NEW HEADERS SHAPE AND |
| | SIZE OF FRAMING AND THE ACTUAL ATTACHMENT OF THE CURB |
| | TO THE ROOF SYSTEM. 1609.6.1.1 MAIN WINDFORCE-RESISTING |
| | SYSTEMS. |
| | |
| | 6B) 301.13 FBC MECHANICAL. WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND |
| | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS |
| | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. THIS CODE SECTION IS NOT ONLY FOR THE |
| | ATTACHMENT OF THE UNIT TO THE STRUCTURAL MEMBERS BUT |
| | THE ACTUAL MECHANICAL EQUIPMENT ITSELF, THE EXTERIOR |
| | CABINETRY. |
| | |
| | 7A) A-4 INDICATES THE USE OF ROOF DRAINS AND OVERFLOW |
| | SCUPPERS THERE IS NO INFORMATION PROVIDED WHAT THE |
| | MINIMUM ROOF INSULATION WILL BE LOCATED AT THE ROOF |
| | DRAINS. FBC 13-404.A.B..1 MINIMUM R-VALUE OF R-10. |
| | |
| | 7B) UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, |
| | DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS SHALL |
| | COMPLY WITH THE FLORIDA BUILDING CODE, PLUMBING , |
| | CHAPTER 11 . |
| | |
| | 8) NOTE PLANS DO NOT INDICATE COMPLIANCE WITH: 1503.6 |
| | PROTECTION AGAINST DECAY AND TERMITES. CONDENSATE LINES |
| | AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT |
| | (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY |
| | UNDERGROUND PIPING, TAIL EXTENSIONS, OR SPLASH BLOCKS. |
| | GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS |
| | WITH EAVES OF LESS THAN 6 INCHES (152 MM) HORIZONTAL |
| | PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF |
| | ABOVE ANOTHER ROOF. |
| | |
| | 9) SHEET S-1 PLEASE INDICATE WHERE THE PROPERTY LINE IS |
| | LOCATED, IT APPEARS THAT THE NEW FOUNDATION SYSTEM NEXT |
| | TO DIXIE HWY MAY BE ENCROUCHING INTO THE RIGHTOF-WAY. |
| | 3202.1.1. STRUCTURAL SUPPORT. A PART OF A BUILDING |
| | ERECTED BELOW GRADE THAT IS NECESSARY FOR STRUCTURAL |
| | SUPPORT OF THE BUILDING OR STRUCTURE SHALL NOT PROJECT |
| | BEYOND THE LOT LINES, EXCEPT THAT THE FOOTINGS OF |
| | STREET WALLS OR THEIR SUPPORTS WHICH ARE LOCATED AT |
| | LEAST 8 FEET (2438 MM) BELOW GRADE SHALL NOT PROJECT |
| | MORE THAN 12 INCHES (305 MM) BEYOND THE STREET LOT |
| | LINE. |
| | |
| | 10) SHEET S-4 PLEASE INDICATE COMPLIANCE WITH 1802.2.1 |
| | QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF |
| | THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY |
| | INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY |
| | WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 11) SHEET S-4 INDICATES THE USE OF A VAPOR BERRIER BUT |
| | NOT SECTION;1816.1 TERMITE PROTECTION. TERMITE |
| | PROTECTION SHALL BE PROVIDED BY REGISTERED |
| | TERMITICIDES, INCLUDING SOIL-APPLIED PESTICIDES, |
| | BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD, OR |
| | OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED |
| | FOR USE AS A PREVENTATIVE TREATMENT TO NEW |
| | CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE. |
| | UPON COMPLETION OF THE APPLICATION OF THE TERMITE |
| | PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL |
| | BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED |
| | PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING |
| | STATEMENT: "THE BUILDING HAS RECEIVED A COMPLETE |
| | TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. |
| | TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS |
| | ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE |
| | AND CONSUMER SERVICES." |
| | |
| | 12) SHEET S-4 CODES AND SPECIFICATIONS ALL WORK SHALL |
| | BE IN ACCORDANCE WITH 2007 FBC HIGH WIND VELOCITY ZONE, |
| | PLEASE NOT THE HIGH VELOCITY WIND ZONE DESIGNATION IS |
| | ONLY TO BE USED FOR DADE AND BROWARD COUNTIES, THE CITY |
| | OF WEST PALM BEACH IS LOCATED IN THE HIGH WIND DEBRIS |
| | REGIONPLEASE REVIEW FIGURE 1609. THE WIND DESIGN FOUND |
| | ON SHEET S-2 INDICATES 146MPH, EXPOSURE "C" WHICH IS A |
| | DADE AND BROWARD REQUIREMENT FOR THE HIGH WIND VELOCITY |
| | ZONE. IF THE DESIGNER WHICHES TO DESIGN TO THIS MORE |
| | STRINGENT REQUIREMENT, THEN THE ASSOCIATED HIGHER |
| | POSITIVE & NEGATIVE PRESSURES MUST |
| | BE USED IN THTE WIND DESIGN. |
| | |
| | 12A) SHEET A-6 DOES INDICATE THE PRESSURES FOR THE |
| | WINDOWS AND DOORS PLEASE PROVIDE INTERIOR ZONES AND END |
| | ZONE LOCATIONS FOR TCLARIFICATION. NOTE ON THE TOWER |
| | PRESSURES ARE NOT INDICATED FOR ALL WINDOW |
| | ELEVATIONS.1609.1.1 |
| | |
| | 12B) SHEET A-4 ROOF PLAN DOES NOT PROVIDE THE ROOF |
| | PRESSURE ZONE LOCATIONS ZONE 1, 2 OR 3 FOR THE FLAT |
| | ROOF NOR THE HIP ROOF. 1609.1.1. |
| | |
| | 12C) SHEET A-6 THE NORTH ELEVATION INDICATES DECRETIVE |
| | SHUTTERS, ISN'T THIS THE MEZZANINE LEVLE WHERE THE |
| | MECHANICAL EQUIPMENT IS LOCATED AND THESE OPENINGS ARE |
| | FOR FRESH AIR NOT A SOLID WALL, IF SO THEY WILL BE |
| | CLASSIFIED AS LOUVERS, PLEASE PROVIDE THE POSISTIVE AND |
| | NEGATIVE PRESSURES FOR OPENINGS. |
| | 1609.1.1. |
| | |
| | 13) SHEET A-7 DOOR D-1 IS INDICATED AS A BY PASS DOOR |
| | PLEASE PROVIDE COMPLIANCE WITH 1008.1.3.3 HORIZONTAL |
| | SLIDING DOORS. |
| | |
| | |
| | 14) PROVIDE INFORMATION ON THE WALK-IN COOLERS AND |
| | FREEZERS. 2603.4.1.2 COOLER AND FREEZER WALLS. FOAM |
| | PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10 INCHES |
| | (254 MM) IN COOLER AND FREEZER WALLS SHALL: |
| | 1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE |
| | TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS. |
| | 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES |
| | OF NOT LESS THAN 600?F AND 800?F (316?C AND 427?C), |
| | RESPECTIVELY. |
| | 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM) |
| | ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE |
| | METAL THICKNESS NOT LESS THAN 0.0160 |
| | INCH (0.4 MM) AT ANY POINT. |
| | 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE |
| | THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE |
| | COOLER OR FREEZER AND THAT PART OF THE |
| | BUILDING IN WHICH IT IS LOCATED SHALL BE SPRINKLERED. |
| | |
| | 2603.4.1.3 WALK-IN COOLERS. IN NONSPRINKLERED |
| | BUILDINGS, FOAM PLASTIC HAVING A THICKNESS THAT DOES |
| | NOT EXCEED 4 INCHES (102 MM) AND A MAXIMUM |
| | FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK-IN |
| | COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR AREA |
| | DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE FOAM |
| | PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN |
| | 0.032-INCH-THICK (0.81 MM) ALUMINUM OR |
| | CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL |
| | THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO |
| | 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A |
| | THERMAL BARRIER. |
| | |
| | 15) SHEET A-7 INDICATES VARIOUS SECTIONS THROUGH THE |
| | STRUCTURE WITH FINISHES( 106.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA FOR COMMERCIAL BUILDINGS ; |
| | 15A) PLANS ARE NOT COMPLETE AS TO INTERIOR FINISHES OF |
| | ROOMS |
| | |
| | 15B) SECTION 803/ TABLE 803.5. |
| | |
| | 15C) PLANS ARE NOT COMPLETE AS TO 1HR FIRE RATING |
| | CEILING, TYPE OF SYSTEM TO BE INSTALLED, 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 15D) INTERIOR WALL AND DOOR SCHEDULE, 106.1.2. |
| | |
| | 16) TRUSS PLANS WERE NOT SUBMITTED, PLANS FAIL TO |
| | PROVIDE LOADS TO BE RESISTED, HORIZONTAL, LATERAL AND |
| | GRAVITY LOADS. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |