| 2009-09-16 19:14:21 | |
| | ** DENIED PLANS** |
| | |
| | |
| | 1) NOTE: THE SUBMITTED FORM B DOES NOT MEET |
| | 13-415.AB.5, 13-415.B.1. THE FORM IS NOT COMPLETED FOR |
| | ANY SPACE OR TYPE OF FIXTURES. THE SPACES ARE IN FACT |
| | BLANK. IN EITHER CASE IF CHOOSING TO USE ALL FORM B*S |
| | FOR COMPLIANCE ONE FORM B IS REQUIRED FOR EACH AND |
| | EVERY SPACE TYPE IN ORDER TO MEET SPACE BY SPACE. |
| | MUST ONLY MEET PRESCRIPTIVE FOR LIGHTING PERFORMANCE |
| | CALCULATIONS. IT IS RECOMMENDED CALLING REVIEWER TO GO |
| | OVER MINIMUM COMPLIANCE. |
| | IF ADDING LIGHTS TO EXISTING THEN LIGHTING COMPLIANCE |
| | IS REQUIRED TO BE SHOWN FOR ALL. |
| | ** THE FIXTURE LEGEND CLEARLY STATES *ALL* FIXTURES ARE |
| | EXISTING HOWEVER PER THE LIGHTING PLANS THERE ARE *NEW* |
| | FIXTURES. HOW ARE ALL FIXTURES EXISTING AND NEW? |
| | |
| | 2) NOTE: PLEASE SEE 422.30,31 FOR REQUIRED |
| | DISCONNECTING MEANS FOR IWH. |
| | PLEASE SEE CIRCUIT 701-3 WHICH IS NOTED ON PANEL |
| | SCHEDULE CONTAINING A LOCK OFF DEVICE. PLEASE SEE |
| | SECTIONS AND COMMENTARY. A DEVICE SHALL BE PERMANENT TO |
| | BREAKER. MUST BE AN INTEGRAL PART OF BREAKER. MAY NOT |
| | BE A *CLIP ON* OR *SNAP ON* TYPE DEVICE. IF THERE IS |
| | ANY NEED TO CLARIFICATION SEE UPDATED COMMENTARY UNDER |
| | THE 2008 NEC. |
| | THE IWH AS CIRCUITED TO 1702.14 DOE NOT CONTAIN ANY |
| | NOTE AS ABOVE. WHERE IS THE REQUIRED DISCONNECTING |
| | MEANS? |
| | |
| | 3) NOTE: NO SOUND LEVELS INDICATED ON FA SHEETS MEETING |
| | ADA COMPLIANCE PER 11-4.28.1,.2 AND .3. |
| | PLEASE PROVIDE. |
| | |
| | 4) NOTE: PLEASE PROVIDE MORE DETAILED INFORMATION ON |
| | NEW LIGHTING CONTROLS( TIME CLOCK) NOTED ON PLANS. |
| | 13-415.AB.1.1,.1.2. |
| | PLEASE ALSO BE AWARE, ALL LIGHTING BEING OVER RIDDEN |
| | SHALL BE SEEN BY THE OCCUPANT OR MEET EXCEPTIONS. ( |
| | PILOT LIGHTS AND INDICATION OF LIGHTING). |
| | |
| | 5) NOTE: PLANS STATE THE *LATEST EDITION* OF THE |
| | NATIONAL ELECTRICAL CODE. HOWEVER PER FS 553.73, RULE |
| | 9B-3.047 THE 2008 HAS NOT YET BEEN ADOPTED BY THE STATE |
| | OF FLORIDA. NOT UNTIL PERMIT APPLICATIONS AFTER OCT |
| | 1ST, 2009. |
| | PLEASE ALSO BE AWARE THERE ARE OTHER REVISIONS TO THE |
| | FBC AT THAT DATE. |
| | PLEASE BE SURE THE PLANS INDICATE THE MINIMUM CODE AS |
| | FOLLOWS. |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | |
| | ** PLANS STATE 2007 FBC ON G-1, HOWEVER THERE ARE 2009 |
| | GLITCHES TO THE 2007 FBC WHICH SUBSTANTIALLY REVISED |
| | THE CODE. |
| | PLANS ALSO STATE THE 2006 FLORIDA FIRE PREVENTION CODE. |
| | THIS SHOULD READ 2007 PER FAC 69A-3.012. REVISED |
| | NFPA-101 AND NFPA-1 IS PER FAC 69A-60.003, .004. |
| | |
| | |
| | |
| | |
| | ** AS STATED ABOVE. PLEASE CALL TO GO OVER ANY |
| | COMMENTS. |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |