2009-09-14 16:41:27RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE RAS 117 SIGNED AND SEALED CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 09-0224.01 SUBMITTED.
  
 2- DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 NEED TO TAKE INTO CONSIDERATION THAT THIS BUILDING IS
 LOCATED ON EXPOSURE "C" AS REQUIRED BY 2009 REVISIONS
 TO FBC 2007 SEC. 1609.4.3.
  
 3- CLEARLY MARK ON NOA SUBMITTED SPECIFIC BASE SHEET
 FASTENING OPTION TO BE USED TO VERIFY COMPLIANCE WITH
 THE UPLIFT LOADS OF SEC. 1609 OF FBC 2007 WITH 2009
 REVISIONS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER