| Plan Review Notes For Permit 09090165 |
| Permit Number |
09090165 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-24 11:42:46 | PERMIT APPLICATION DESCRIBES THE WORK AS "MULTI-STORY | | | TOWNHOMES PROVIDING FIRE ALARM FOR THE REMEDIATION AND | | | FINISHING OF THE INDIVIDUAL TOWN HOME UNITS AND COMMON | | | AREA". | | | | | | 1. IT HAS BEEN REPORTED TO THIS OFFICE THAT THE FIRE | | | ALARM EQUIPMENT HAS ALREADY BEEN INSTALLED WITHOUT | | | APPROVED PLANS AND A PERMIT. NO INSTALLATION OF THIS | | | EQUIPMENT SHOULD HAVE OCCURRED WITHOUT A REVIEW OF | | | PLANS AND RECEIVING A PERMIT FROM THE CITY OF WEST PALM | | | BEACH. | | | | | | 2. THE FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY A UL | | | LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION | | | SERVICE AS DESCRIBED ON PAGE 2 OF 2. | | | | | | 3. WHY IS ONLY HORN STROBE DEVICE SHOWN ON BUILDING AND | | | NOT THE OTHER. | | | | | | 4. THE PERMIT APPLICATIONS FOR BOTH BUILDINGS INDICATE | | | A VALUE OF $ 1,000 DOLLARS. HOW CAN THAT BE WHEN | | | BUILDING HAS A PANEL AND THE OTHER ONE DOES NOT. | | | | | | 5. SHOULD THE FIRE ALARM SYSTEM BE DOWN BOTH BUILDINGS | | | WILL REQUIRE A FIRE WATCH INSTEAD OF ONLY ONE SINCE | | | ONLY ONE PANEL IS BEING INSTALLED. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | WEST PALM BEACH FIRE RESCUE | | | 500 NORTH DIXIE HIGHWAY | | | WEST PALM BEACH, FLORIDA 33401 | | | 804-4709 PHONE | | | 804-4774 FAX | | | MCARSILLO@WPB,ORG |
|