| Plan Review Notes For Permit 09090164 |
| Permit Number |
09090164 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-11-25 06:47:40 | REVISED PLANS ILLUSTRATE A RADIO TRANSMITTOR TO BE USED | | | AS A COMMUNICATOR FOR THE FIRE ALARM SYSTEM. THIS | | | ARRANGEMENT IS NOT APPROVED. TWO TELEPHONE LINES WITH | | | RJ31X TELEPHONE JACKS ARE REQUIRED. | | | | | | PLEASE SUBMIT REVISED PLANS. | | | | | | PLEASE BE ADVISED THAT THE NEXT REVIEW WILL BE THE | | | THIRD REVIEW FOR THESE PLANS. | | | | | | | | | DENIED. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | (561) 804-4709 PHONE | | | (561) 804-4774 FAX |
|