Text |
| 2009-12-09 08:57:24 | ** DENIED ** |
| | |
| | ** SETS OF PLANS SUBMITTED ARE NOT THE SAME. |
| | ONE SET HAD ALL COMPLETE ELECTRICAL PAGES WHICH WERE |
| | NOT REQUESTED ON PREVIOUS REVIEW. |
| | ONE SET HAS PLUMBING SHEETS WHICH ARE NOT IN THE SECOND |
| | SET?? |
| | |
| | |
| | 2ND REQUEST |
| | 1) NOTE: PLEASE PROVIDE INFORMATION ON THE TYPE OF BACK |
| | UP SYSTEM OF THIS GENERATOR. PLEASE SEE DEFINITIONS IN |
| | NEC/ NFPA-70 2008, 700,701, AND 702. |
| | PLEASE ALSO SEE 2005 NFPA-110. |
| | THE BASE BUILDING PLANS WERE ALSO SUBMITTED HOWEVER NOT |
| | ALL EMERGENCY LIGHTS ON THE FIXTURE LEGEND INDICATE |
| | BATTERY BACK UP. ALL REQUIRED EMERGENCY BACK UP POWER |
| | MUST BE FED FROM 700 OR 701 SYSTEMS. IF BATTERY BACK UP |
| | POWER IS PROVIDED FOR ALL LIFE SAFETY AND LEGALLY |
| | REQUIRED THEN THIS SYSTEM WOULD BE OPTION STAND-BY. |
| | IF THIS IS A 700 OR 701 SYSTEM IT MAY NOT RELY ON |
| | NATURAL GAS AS THE PRIMARY SOURCE FOR THE PRIME MOVER. |
| | 700.12B3, 701.11B3. |
| | PLEASE REDESIGN SYSTEM IF INDEED FALLING UNDER NFPA-70, |
| | 700,701 OR NFPA-110 |
| | |
| | ** THERE WAS NO RESPONSE FROM THE DESIGNER OF RECORD TO |
| | PREVIOUS ELECTRICAL REVIEW COMMENTS. A CALL WAS PLACED |
| | TO THE ARCHITECT OF RECORD AS THE PHONE NUMBER LISTED |
| | ON TITLE BLOCK IS NO LONGER IN USE. NEW NUMBER FOR |
| | ENGINEER WAS OBTAINED FROM ARCHITECT AND LEFT MESSAGE |
| | ON 12/8 FOR A RETURN CALL. |
| | |
| | PLANS WILL REMAIN IN FAILED STATUS UNTIL INFORMATION IS |
| | PROVIDED OR PLANS ARE REVISED. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |