| Notes |
| Date |
Text |
| 2009-09-22 16:50:13 | 2007 FBC W/2009 REVISIONS | | | LEVEL 1 ALTERATION | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY THE SIZE AND TYPE OF EACH OF THE WINDOWS ON | | | THE FLOOR PLAN. FOR EXAMPLE SH 35, 24" X 24" FIXED OR | | | (2) SH 35 WHEN 2 WINDOWS ARE MULLED TOGETHER. FBC | | | R301.2.1 | | | | | | 2) SPECIFY THE SIZE AND TYPE OF EACH DOOR BEING | | | REPLACED. FOR EXAMPLE 3/0 X 6/8 DOUBLE OUTSWING GLAZED | | | FRENCH DOORS. FBC R301.2.1 | | | | | | 3) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL MULLIONS | | | THAT WILL BE USED TO CONNECT MULTIPLE WINDOWS INSTALLED | | | IN THE SAME OPENING. REQUIRED BY DCA RULE 9B-72. | | | | | | 4) PLEASE CIRCLE THE GLASS TYPE AND SIZES OF NEW | | | WINDOWS AND DOORS AND THEIR THE DESIGN PRESSURES FROM | | | THE TABLES IN THE PRODUCT APPROVAL NOA. FBC R301.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|