| Plan Review Notes For Permit 09090065 |
| Permit Number |
09090065 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-02-02 09:59:05 | ** PROVISO* | | | | | | ** THE FOLLOWING IS TO BE REVISED AND SUBMITTED FOR | | | REVIEW AND STAMPING BEFORE ANY INSPECTION IS SCHEDULED. | | | IF PLANS GO BACK FOR OTHER CORRECTIONS THESE | | | CORRECTIONS MAY BE DONE AT THAT TIME. | | | | | | 1) NOTE: RISER AND PLANS BOTH INDICATE *EQUIPMENT | | | GROUNDING CONDUCTOR* FROM FPL TO THE METER. THIS IS NOT | | | PERMITTED. THIS WOULD PARALLEL THE NEUTRAL ( GROUNDED) | | | CONDUCTOR THUS CREATING OBJECTIONABLE CURRENTS. | | | 250.24, 250.6 | | | | | | 2) NOTE: THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR | | | IS TOO SMALL. SHOWN AS #10, HOWEVER PER 250.66 OF THE | | | NEC, THE SMALLEST CONDUCTOR PERMITTED IS #8. | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|