Plan Review Notes
Plan Review Notes For Permit 09090065
Permit Number 09090065
Review Stop E
Sequence Number 2
Notes
Date Text
2010-02-02 09:59:05** PROVISO*
  
 ** THE FOLLOWING IS TO BE REVISED AND SUBMITTED FOR
 REVIEW AND STAMPING BEFORE ANY INSPECTION IS SCHEDULED.
 IF PLANS GO BACK FOR OTHER CORRECTIONS THESE
 CORRECTIONS MAY BE DONE AT THAT TIME.
  
 1) NOTE: RISER AND PLANS BOTH INDICATE *EQUIPMENT
 GROUNDING CONDUCTOR* FROM FPL TO THE METER. THIS IS NOT
 PERMITTED. THIS WOULD PARALLEL THE NEUTRAL ( GROUNDED)
 CONDUCTOR THUS CREATING OBJECTIONABLE CURRENTS.
 250.24, 250.6
  
 2) NOTE: THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR
 IS TOO SMALL. SHOWN AS #10, HOWEVER PER 250.66 OF THE
 NEC, THE SMALLEST CONDUCTOR PERMITTED IS #8.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  