| 2010-02-03 15:52:54 | BUILDING PLAN REVIEW |
| | PERMIT: 09090065 |
| | ADD: 8537 NORTHLAKE BLVD |
| | CONT: "TO BE DETERMINED" |
| | TEL: (561)494-1088 DANIEL ROBERGE |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | FEB. 03/ 2010 |
| | |
| | 1)COMPLIED. |
| | |
| | 2)2ND REQUEST, PLANS ARE INDICATED TO BE DESIGNED BY |
| | P.E. DANIEL ROBERGE, PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| | BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE |
| | AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| | DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS. |
| | |
| | 3)COMPLIED. WORK DELETED. |
| | |
| | 4) 2ND REQUEST, SHEET 11 OF 17 NOTE ON PLANS INDICATE |
| | TTHE USE OF A TWO ROW BOND BEAM OVER THE GLASS WINDOWS, |
| | THIS CAN BE ACCOMPLISHED THE ELEVATIONS ON SHEET 9 &10 |
| | INDICATE THE USE OF A BOND BEAM CONSTRUCTION, THE WAY |
| | THE ELEVATION APPEARS THE INTENT IS TO USE STEEL POWER |
| | LINTELS INSTEAD OF A PRECAST CONCRETE LINTEL, PLEASE |
| | PROVIDE THE MANUFACTURES SPEC FOR THE TYPE OF LINTERL |
| | TO BE INSTALLED. 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 5A ) GLASS BLOCK- COMPLIED |
| | 5B) EXTERIOR SWING DOORS- COMPLIED. |
| | 5C) WALL LOUVERS- CONCRETE-NO PRODUCT APRROVALS WERE |
| | SUBMITTED ONLY A CUT SHEET! |
| | 5D) LINTELS- NO PRODUCT APPOVALS WERE SUBMITTED |
| | 5E) TRUSS ANCHORS- COMPLIED. |
| | F) ROOF ASSEMBLIES-COMPLIED. |
| | G) SKYLIGHTS- LARGE MISSILE TESTED GLAZED OPENING!- |
| | COMPLIED. |
| | |
| | 6) 2ND REQUEST, 106.3.3 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72 |
| | SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 7) NEW COMMENT, THE LOCATION OF THE RESTROOMS IS A |
| | DESIGNATED "A" FLOOD ZONE WITH AN UNKNOWN FLOOD LEVEL. |
| | THE ENGINEERING DEPARTMENT IS TO SET THE HEIGHT FOR |
| | FINISH |
| | FLOOR AS WELL AS A FLOOD ZONE CERTIFICATE AT TIME OF |
| | THE FLOOR SLAB POUR. FBC BUILDING 3110.1.2 / CITY OF |
| | WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS |
| | LOCATED IN AN "A" FLOOD ZONE. A FLOOD ELEVATION |
| | CERTIFICATE WILL BE REQUIRED. |
| | |
| | 8) THE WIND DESIGN CRITERIA FOR THIS BUILDING HAS NEVER |
| | BEEN SUBMITTED, ONLY FOR THE STRUCTURES SHOWN ON SHEET |
| | 7 OF 17 WHICH WAS CANCELLED. PLEASE NOTE THE NEW |
| | LOCATION OF THE RESTROOM WILL PLACE THE STRUCTURE IN |
| | "C" EXPOSURE WITH HIGHER PRESSURES THAN PROVIDED AS A |
| | "B" EXPOSURE. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |