Plan Review Notes
Plan Review Notes For Permit 09090065
Permit Number 09090065
Review Stop B
Sequence Number 2
Notes
Date Text
2010-02-03 15:52:54BUILDING PLAN REVIEW
 PERMIT: 09090065
 ADD: 8537 NORTHLAKE BLVD
 CONT: "TO BE DETERMINED"
 TEL: (561)494-1088 DANIEL ROBERGE
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 FEB. 03/ 2010
  
 1)COMPLIED.
  
 2)2ND REQUEST, PLANS ARE INDICATED TO BE DESIGNED BY
 P.E. DANIEL ROBERGE, PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS.
  
 3)COMPLIED. WORK DELETED.
  
 4) 2ND REQUEST, SHEET 11 OF 17 NOTE ON PLANS INDICATE
 TTHE USE OF A TWO ROW BOND BEAM OVER THE GLASS WINDOWS,
 THIS CAN BE ACCOMPLISHED THE ELEVATIONS ON SHEET 9 &10
 INDICATE THE USE OF A BOND BEAM CONSTRUCTION, THE WAY
 THE ELEVATION APPEARS THE INTENT IS TO USE STEEL POWER
 LINTELS INSTEAD OF A PRECAST CONCRETE LINTEL, PLEASE
 PROVIDE THE MANUFACTURES SPEC FOR THE TYPE OF LINTERL
 TO BE INSTALLED. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 5A ) GLASS BLOCK- COMPLIED
 5B) EXTERIOR SWING DOORS- COMPLIED.
 5C) WALL LOUVERS- CONCRETE-NO PRODUCT APRROVALS WERE
 SUBMITTED ONLY A CUT SHEET!
 5D) LINTELS- NO PRODUCT APPOVALS WERE SUBMITTED
 5E) TRUSS ANCHORS- COMPLIED.
 F) ROOF ASSEMBLIES-COMPLIED.
 G) SKYLIGHTS- LARGE MISSILE TESTED GLAZED OPENING!-
 COMPLIED.
  
 6) 2ND REQUEST, 106.3.3 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 7) NEW COMMENT, THE LOCATION OF THE RESTROOMS IS A
 DESIGNATED "A" FLOOD ZONE WITH AN UNKNOWN FLOOD LEVEL.
 THE ENGINEERING DEPARTMENT IS TO SET THE HEIGHT FOR
 FINISH
 FLOOR AS WELL AS A FLOOD ZONE CERTIFICATE AT TIME OF
 THE FLOOR SLAB POUR. FBC BUILDING 3110.1.2 / CITY OF
 WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS
 LOCATED IN AN "A" FLOOD ZONE. A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED.
  
 8) THE WIND DESIGN CRITERIA FOR THIS BUILDING HAS NEVER
 BEEN SUBMITTED, ONLY FOR THE STRUCTURES SHOWN ON SHEET
 7 OF 17 WHICH WAS CANCELLED. PLEASE NOTE THE NEW
 LOCATION OF THE RESTROOM WILL PLACE THE STRUCTURE IN
 "C" EXPOSURE WITH HIGHER PRESSURES THAN PROVIDED AS A
 "B" EXPOSURE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  