Plan Review Notes
Plan Review Notes For Permit 09090065
Permit Number 09090065
Review Stop ENG
Sequence Number 1
Notes
Date Text
2009-10-19 13:55:01FAILED
 PLANS REQUIRED REVISIONS
  
 THE PLANS ARE STAMPED ON THE FRONT SHEET THAT THEY NEED
 TO APPLY FOR A PLUMBING PERMIT. ALONG THOSE LINES WE
 NEED TO STATE THEY NEED TO SHOW ON THE PLAN BEFORE IT
 IS SUBMITTED TO CONSTRUCTION SERVICES THE FOLLOWING
 CHANGES;
 SHEET 12:
  BACKFLOW PREVENTER NEEDS TO BE INSTALLED AT THE METER.
  SIZE METER
  SIZE CITY WATER SERVICE
  SIZE PIPING TO THE BATHROOM (2" IS SHOWN AND MAY NOT
 BE REQUIRED FOR TWO TOILETS AND TWO SINKS)
  CHANGE PIPE MATERIAL FROM COPPER TYPE "K" TO PVC
  STATE FLOOR ELEVATION OF BATHROOM AND RIM ELEVATION OF
 THE MANHOLE AND THE TOP OF LIFT STATION.
  THIS IS TO BE SURE THAT IF THE SEWER BACKS UP, IT
 DOES NOT BACK UP INTO THE BATHROOMS.
  CLEAN OUT REQUIRED WHERE THE LATERAL LEAVES THE
 BATHROOM. DEPENDING ON THE LENGTH OF RUN
  FROM THE BATHROOM TO THE MANHOLE TO BE TIED TO THE
 LATERAL NEEDS TO HAVE CLEAN-OUTS INSTALLED
  A MINIMUM OF EVERY 100' AND AT EVERY BEND.
 MY NOTE ON THE PLANS TO INSTALL THE CONTROL PANEL FOR
 THE LIFT STATION ON THE WALL OF THE BATHROOM IS NO
 LONGER VALID.
 MY NOTE ON THE WATER SERVICE TO THE LIFT STATION IS
 INVALID.
  
 OTHER NOTES (YOURS AND MINE) THAT ARE STILL VALID:
 SHEET 3:
 SHOW LOCATION OF SHELTER/CLASS ROOM.
 REMOVE DETAIL SHOWING FORCE MAIN TIE-IN AT NORTHLAKE,
 IT IS NOT REQUIRED
 SHOW CORING INTO EXISTING MANHOLE FOR LATERAL TO NEW
 BATHROOM
 PROVIDE RIM AND INVERT OF EXISTING MANHOLE TO BE TIED
 TO
 PROVIDE ELEVATION OF PROPOSED LATERAL TO BE TIED INTO
 MANHOLE
 SHOW LOCATION OF NEW BATHROOM
 SHEET 4:
 SHOW WATER LINE FROM BATHROOM TO METER
 REMOVE NOTE: FIBERGLASS STRUCTURE TO BE REMOVED (BY
 OTHERS). THIS NOTE IS NOT REQUIRED.
 SHEET 6:
 SHELTER LOCATION IS NOT SHOWN ON PLAN (SEE SHEET 3)
 YOU SHOW THE NEW ROAD SURFACE TO BE INSTALLED FLAT. IT
 SHOULD BE SLOPED OFF TO EITHER SIDE OR TO ONE SIDE AT A
 2% SLOPE.
 WHAT IS THE FLOOR ELEVATION OF THE SHELTER?
 SHOULD THE FLOOR HAVE A 2% SLOPE FROM THE CENTER OUT SO
 THERE IS NO PONDING OF WATER DURING OR AFTER A RAIN
 STORM.
 WHAT IS THE EXISTING GRADE AROUND THE SHELTER, IT
 SHOULD BE BUILT UP AT LEAST 6" FROM THE SURROUNDING
 ELEVATIONS AND THE EXISTING ELEVATIONS SHOULD BE GRADED
 AWAY FROM THE SHELTER.
 YOU HAVE A NOTE FOR THE CONCRETE BASE FOR EMERGENCY
 PHONE, WHERE IS THE DETAIL, IT NEEDS TO BE ON THE SAME
 SHEET.
 THE DETAIL FOR THE 6" SQUARE PINE POSTS FOR THE SHELTER
 HAVE NO DEPTH ON THEM. THE CONCRETE IS TO BE 3.5' DEEP,
 BUT HOW MUCH CONCRETE IS UNDER THE POSTS?
 ARE THE 6" SQUARE PINE POSTS TO BE PRESSURE TREATED?
 SHEET 7:
 WHAT IS THE OVER HANG ON THE ROOF OF THE KIOSKS?
  