| 2009-09-24 08:53:17 | |
| | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE: PLANS NEED TO BE UNDER PERMIT APPLICATION BY A |
| | LICENSED CONTRACTOR BEFORE A REVIEW STATUS CAN BE IN |
| | PASSED EVEN ONCE PLANS ARE FOUND TO BE REVIEWED FOR |
| | CODE COMPLIANCE. |
| | ** PLANS ALSO NEED TO STATE CODEC IN WHICH DESIGN IS |
| | UNDER. PLEASE KEEP IN MIND THAT SINCE PERMIT |
| | APPLICATION IS NOT MADE, ALL PERMIT APPLICATIONS AS OF |
| | OCT 1ST, 2009 WILL BE UNDER THE 2008 NEC. |
| | |
| | 2) NOTE: PLANS DO CONTAIN A DESIGN PROFESSIONAL ON |
| | TITLE BLOCKS HOWEVER NO SIGNATURE DATE OR SEAL PER FS |
| | 471.025. |
| | TITLE BLOCKS ALSO NEED TO BE COMPLETE WITH ALL |
| | INFORMATION PER FAC 61G15-23.002. |
| | |
| | 3) NOTE: PLANS CONTAIN NOTES TO INSTALL NEW FEED TO |
| | PANELS AND METER FROM EXISTING PANEL ON WOOD BOARD |
| | HOWEVER WHAT KIND OF METER WILL THIS BE? IF FEED IS |
| | FROM ANOTHER PANEL THEN THIS IS NOT AN FPL METER. |
| | |
| | NO RISER DIAGRAM SUBMITTED FOR REVIEW. PLEASE SUBMIT A |
| | COMPLETE RISER MEETING NEC MINIMUM COMPLIANCE. |
| | PLEASE SEE 230.70, .71, 250.50, 110.9, 215.5, ETC IF |
| | THIS IS A NEW SERVICE FROM FPL |
| | PLEASE SEE |
| | PLEASE SEE 225.31-225.39 IF THIS IS GOING TO FED FROM |
| | AN EXISTING SERVICE OR EQUIPMENT. |
| | PLEASE SEE 250.50, 250.32 FOR DETACHED STRUCTURES. |
| | |
| | 4) NOTE: PLEASE BE SURE TO SHOW ALL CIRCUITING ON PLANS |
| | AND COORDINATE WITH PANEL SCHEDULE TO BE SUBMITTED. |
| | 408.4. PLEASE BE SURE ALL OVER CURRENT PROTECTION |
| | DEVICES ARE SHOWN WITH CORRECT WIRING SIZES. |
| | 240.4,310.16 |
| | |
| | 5) NOTE: PLEASE SEE FBC 13-415.AB.1.4 FOR REQUIRED |
| | EXTERIOR LIGHTING CONTROLS. |
| | |
| | ** PLEASE COMPLETE PLANS. AS THERE ARE SEVERAL ITEMS |
| | NOT YET SHOWN ON PLANS FOR MINIMUM COMPLIANCE A REVIEW |
| | OF THOSE ITEMS CAN NOT BE DONE. WHEN PLANS ARE |
| | SUBMITTED BACK THERE MAY BE NEW COMMENTS WHICH CAN NOT |
| | BE MADE AT THIS TIME. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |