| Plan Review Notes For Permit 09090030 |
| Permit Number |
09090030 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-18 16:37:44 | | | | 1. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS | | | FOR HANDRAILS. | | | | | | 2. GAS PIPING AND APPURTENANT EQUIPMENT SHALL COMPLY | | | WITH THE APPROPRIATE NFPA STANDARDS. INSTALLATION SHALL | | | BE PERFORMED TO RECOGNIZED STANDARDS AND IN A SAFE | | | MANNER. | | | | | | 3. THE INSTALLATION OF ANY EQUIPMENT SHALL NOT | | | INTERFERE WITH ANY EXITING, EXIT ACCESS OR ACCESS TO | | | ANY FIRE SAFETY EQUIPMENT. THIS EQUIPMENT WOULD INCLUDE | | | ANY ROOF MANIFOLDS FOR THE STANDPIPE SYSTEM. | | | | | | 4. NO DETAILS ON FIRESTOPPING METHODS, MATERIALS, OR | | | MANNER PLANNED TO BE USED WHEN PENETRATING RATED FLOORS | | | OR WALLS. | | | | | | 5. NO EQUIPMENT SHALL BE ROUTED THROUGH ANY STAIRWELLS. | | | | | | 6. PLEASE INDICATE RISE, RUN, AND TREAD DEPTH FOR THE | | | PLATFORM STAIRS. WHAT MEASURES WILL BE USED TO PROVIDE | | | SLIP PREVENTION. | | | | | | 7. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX | | | |
|