Plan Review Notes
Plan Review Notes For Permit 09090030
Permit Number 09090030
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-09-18 16:37:44 
 1. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS.
  
 2. GAS PIPING AND APPURTENANT EQUIPMENT SHALL COMPLY
 WITH THE APPROPRIATE NFPA STANDARDS. INSTALLATION SHALL
 BE PERFORMED TO RECOGNIZED STANDARDS AND IN A SAFE
 MANNER.
  
 3. THE INSTALLATION OF ANY EQUIPMENT SHALL NOT
 INTERFERE WITH ANY EXITING, EXIT ACCESS OR ACCESS TO
 ANY FIRE SAFETY EQUIPMENT. THIS EQUIPMENT WOULD INCLUDE
 ANY ROOF MANIFOLDS FOR THE STANDPIPE SYSTEM.
  
 4. NO DETAILS ON FIRESTOPPING METHODS, MATERIALS, OR
 MANNER PLANNED TO BE USED WHEN PENETRATING RATED FLOORS
 OR WALLS.
  
 5. NO EQUIPMENT SHALL BE ROUTED THROUGH ANY STAIRWELLS.
  
 6. PLEASE INDICATE RISE, RUN, AND TREAD DEPTH FOR THE
 PLATFORM STAIRS. WHAT MEASURES WILL BE USED TO PROVIDE
 SLIP PREVENTION.
  
 7. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
  