2009-09-24 08:23:02** DENIED **
  
  
  
 1) NOTE: PLEASE SEE 445.18 AND PROVIDE METHOD TO
 COMPLY. PLEASE KEEP IN MIND A SHUNT TRIP TYPE BREAKER
 IS NOT ACCEPTABLE. IN AN EMERGENCY SITUATION AND POWER
 IN THE BUILDING NEEDS TO BE SHUT DOWN, THERE IS NOT WAY
 FOR FIRE DEPARTMENT OR OTHER PERSONAL TO SHUT DOWN
 GENERATOR UNLESS GOING TO THE ROOF TO DO SO.
 A READILY ACCESSIBLE MEANS OF SHUTTING DOWN PRIME MOVER
 SUPPLY MUST BE INSTALLED IN CLOSE PROXIMITY TO THE MAIN
 ELECTRICAL ROOM/FIRE COMMAND ROOM WHEN LOCATED ON SITE.
 A GENERATOR STATUS PANEL MUST ALSO INDICATE THE UNIT
 STATUS.
 PLEASE ALSO PLACE NOTES ON PLANS FOR REQUIRED SIGNAGE
 AT ALL OF THE ABOVE LOCATIONS.
  
 2) NOTE: THE PROPOSED VALUE IS LOW. THE VALUE IS
 REQUIRED TO INCLUDE THE FOLLOWING EVEN IF ANY OF THESE
 ARE OWNER SUPPLIED.
 DESIGN/PLANS FEE.
 ALL LABOR,
 ALL EQUIPMENT, ( GENERATOR AND ATS)
 ALL MATERIALS ETC
  
 FBC 108.3
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  