| Plan Review Notes For Permit 09090030 |
| Permit Number |
09090030 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-24 08:23:02 | ** DENIED ** | | | | | | | | | | | | 1) NOTE: PLEASE SEE 445.18 AND PROVIDE METHOD TO | | | COMPLY. PLEASE KEEP IN MIND A SHUNT TRIP TYPE BREAKER | | | IS NOT ACCEPTABLE. IN AN EMERGENCY SITUATION AND POWER | | | IN THE BUILDING NEEDS TO BE SHUT DOWN, THERE IS NOT WAY | | | FOR FIRE DEPARTMENT OR OTHER PERSONAL TO SHUT DOWN | | | GENERATOR UNLESS GOING TO THE ROOF TO DO SO. | | | A READILY ACCESSIBLE MEANS OF SHUTTING DOWN PRIME MOVER | | | SUPPLY MUST BE INSTALLED IN CLOSE PROXIMITY TO THE MAIN | | | ELECTRICAL ROOM/FIRE COMMAND ROOM WHEN LOCATED ON SITE. | | | A GENERATOR STATUS PANEL MUST ALSO INDICATE THE UNIT | | | STATUS. | | | PLEASE ALSO PLACE NOTES ON PLANS FOR REQUIRED SIGNAGE | | | AT ALL OF THE ABOVE LOCATIONS. | | | | | | 2) NOTE: THE PROPOSED VALUE IS LOW. THE VALUE IS | | | REQUIRED TO INCLUDE THE FOLLOWING EVEN IF ANY OF THESE | | | ARE OWNER SUPPLIED. | | | DESIGN/PLANS FEE. | | | ALL LABOR, | | | ALL EQUIPMENT, ( GENERATOR AND ATS) | | | ALL MATERIALS ETC | | | | | | FBC 108.3 | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|