Plan Review Notes
Plan Review Notes For Permit 09090030
Permit Number 09090030
Review Stop B
Sequence Number 1
Notes
Date Text
2009-09-22 13:25:07BUILDING PLAN REVIEW
 PERMIT: 09090030
 ADD: 1200 S FLAGLER DR/ ROOFTOP
 CONT: J. CROMPTON ELECTRIC, INC
 TEL: (321)288-7093
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) S-2 DETAIL# 2 INDICATES THE RISE ON THE STAIRS AS 10
 INCHES, PLEASE REVIEW SECTION 1009.3 EXCEPTION# 6.
  
 2) S-3 DETAIL# 2 INDICATES A CROSS OVER BRIDGE
 ELEVATION, 106.1.2 ADDITIONAL INFORMATION REQUIRED,
 THERE IS NO INFORMATION AS TO MATERIALS AND DIMENSIONS.
  
 3) S-3 DETAIL# 2 ALSO DOES NOT INDICATE HOW THE CROSS
 OVER BRIDGE IS GOING TO BE FASTENED TO THE PRECAST
 FIBERCRETE PAD NOR HOW THE BRIDGE IS GOING TO RESIST
 THE MOMENT OF OVERTURNING.
 1604.4 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY LATERAL FORCES SPECIFIED
 IN THIS CHAPTER. SEE SECTION 1609 FOR WIND .
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  