Plan Review Notes
Plan Review Notes For Permit 09080800
Permit Number 09080800
Review Stop G
Sequence Number 1
Notes
Date Text
2009-08-31 15:03:08DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
 FBC-2007 FUEL GAS
  
 1. PIPE SIZE FROM THE METER TO BE 2 INCH SCHED 40 GALV.
 PIPE. PLEASE INDICATE PIPE SIZE & MATERIAL. TABLE
 402.4(2)
  
 2. PIPE SIZE TO INSIDE THE HOUSE TO BE A MINIMUM 1
 INCH. TABLE 402.4(2).
  
 3. OTHER PIPE SIZES WILL HAVE TO BE CHANGED INSIDE THE
 HOUSE AS THERE HAS BEEN ABOUT 50 MORE FEET ADDED TO THE
 SYSTEM. SECTION 402.
  
 4. THE PIPE SIZE FOR THE P.E. PIPE TO THE POOL HEATER
 WILL NEED TO BE INCREASED TO 1-1/2" FROM 1-1/4". TABLE
 401.4(19).
  
 5. INDICATE THE PIPE SIZE FROM THE METER TO THE FIRST
 TEE AND SHOW PIPE SIZE FROM THE FIRST TEE TO THE SECOND
 TEE. SECTION 402.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved