| Plan Review Notes For Permit 09080783 |
| Permit Number |
09080783 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-01 10:30:37 | 2007 FBC W/2007 REVISIONS | | | RE-ROOF | | | | | | DENIED BY BUILDING | | | | | | 1) THE PRODUCT APPROVAL COVER-SHEETS THAT WERE | | | SUBMITTED FOR THE TU PLUS UNDERLAYMENT AND MONIER | | | CONCRETE ROOF TILE ARE FOR THE 2004 FLORIDA BUILDING | | | CODE WHICH IS NO LONGER IN EFFECT. THE CURRENT CODE IS | | | THE 2007 FBC. SUBMIT CURRENT PRODUCT APPROVALS. DCA | | | RULE 9B-72. | | | | | | 2) IN ADDITION TO THE FLORIDA PRODUCT APPROVAL COVER | | | SHEETS, THE INSTALLATION AND EVALUATION INFORMATION FOR | | | THE PRODUCT IS REQUIRED PER DCA RULE 9B-72. SUBMIT THIS | | | ADDITIONAL INFORMATION OR THE MIAMI-DADE NOA FOR THE | | | PRODUCTS. | | | | | | 3) THE MIAMI-DADE NOA FOR THE POLYGLASS MODIFIED | | | ROOFING MATERIAL HAS BEEN CLOSED BY THE MIAMI-DADE CODE | | | COMPLIANCE OFFICE. SUBMIT TWO COPIES OF A CURRENT | | | PRODUCT APPROVAL. SPECIFY THE FASTENING OPTION AND | | | DESIGN PRESSURES FOR THE SYSTEM TO BE INSTALLED. SUBMIT | | | RAS 117 CALCULATIONS FOR ENHANCED FASTENING AT CORNER | | | AND PERIMETER AREAS. SEE LIMITATIONS ON THE PRODUCT | | | APPROVALS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|