| Plan Review Notes For Permit 09080726 |
| Permit Number |
09080726 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-14 09:20:32 | | | | | | | ** DENIED PLANS ** | | | | | | | | | 1) NOTE: COPIES OF SIGNED, DATED AND SEALED PLANS DONE | | | BY AN ENGINEER IS NOT PERMITTED. PLEASE SEE FS 471.025, | | | FAC 61G15-23.002. PLANS MUST BE DONE BY DESIGN | | | PROFESSIONAL MEETING 471, OR 471.003 EXCEPTIONS. THIS | | | EXCEPTION MAY BE A LICENSED CONTRACTOR UNDER FS 489. | | | PLEASE RE-DRAW PLANS, PRINT NAME AND SIGN. | | | | | | ** PLANS SHOULD ONLY INDICATE THE SCOPE OF WORK BEING | | | APPLIED FOR UNDER PERMIT APPLICATION. | | | | | | 2) NOTE: THERE IS NO CODE DESIGN INFORMATION ON PLANS. | | | THE STATE IS CURRENTLY UNDER THE 2005 NFPA-70 AND 2006 | | | NFPA-101. | | | THERE IS NO INFORMATION ON PLANS FOR ACCESS CONTROL | | | SYSTEM. NO INFORMATION ON FAIL SAFE OPERATION OF SYSTEM | | | WHICH SHALL NO IMPEDE EGRESS UNDER NORMAL OR EMERGENCY | | | CONDITIONS. | | | PLEASE SEE NFPA-101 CHAPTER 7. PLEASE SEE 7.2, 7.2.1.5, | | | 7.2.1.6.2 ETC. | | | | | | | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|