| Plan Review Notes For Permit 09080706 |
| Permit Number |
09080706 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-21 08:47:21 | | | | ** DENIED ** | | | PERMIT APPLICATION HAS NOT BEEN MADE. A PROVISO COULD | | | HAVE POSSIBLY ISSUED ONLY IF PERMIT APPLICATION HAD | | | BEEN MADE. | | | | | | | | | | | | 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR BY A LICENSED | | | CONTRACTOR. AS OF OCTOBER 1ST, 2009 THE 2008 NEC/ | | | NFPA-70 WILL GO INTO AFFECT. THIS WILL SUBSTANTIALLY | | | CHANGE MANY ITEMS SHOWN ON PLANS INCLUDING ITEMS UNDER | | | THE NEW CODE WHICH WILL BE CONSIDERED LIFE SAFETY BY | | | NFPA. | | | | | | 2) NOTE: PLANS DO NOT INDICATE ANY CARBON MONOXIDE | | | DETECTORS/ALARMS. PLEASE SEE FS 553.885. PLEASE REVISE | | | IF ADDITION OF GAS APPLIANCES GOING TO BE ADDED. | | | | | | 3) NOTE: PLEASE SEE FBC R313.1 PLEASE PROVIDE LAYOUT OF | | | EXISTING OR NEW SMOKE ALARMS MEETING NFPA-72 | | | 11.5.1,11.8.3 | | | | | | ** MAY USE COMBONATION DEVICES. | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|