Plan Review Notes
Plan Review Notes For Permit 09080706
Permit Number 09080706
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-21 08:47:21 
 ** DENIED **
 PERMIT APPLICATION HAS NOT BEEN MADE. A PROVISO COULD
 HAVE POSSIBLY ISSUED ONLY IF PERMIT APPLICATION HAD
 BEEN MADE.
  
  
  
 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR BY A LICENSED
 CONTRACTOR. AS OF OCTOBER 1ST, 2009 THE 2008 NEC/
 NFPA-70 WILL GO INTO AFFECT. THIS WILL SUBSTANTIALLY
 CHANGE MANY ITEMS SHOWN ON PLANS INCLUDING ITEMS UNDER
 THE NEW CODE WHICH WILL BE CONSIDERED LIFE SAFETY BY
 NFPA.
  
 2) NOTE: PLANS DO NOT INDICATE ANY CARBON MONOXIDE
 DETECTORS/ALARMS. PLEASE SEE FS 553.885. PLEASE REVISE
 IF ADDITION OF GAS APPLIANCES GOING TO BE ADDED.
  
 3) NOTE: PLEASE SEE FBC R313.1 PLEASE PROVIDE LAYOUT OF
 EXISTING OR NEW SMOKE ALARMS MEETING NFPA-72
 11.5.1,11.8.3
  
 ** MAY USE COMBONATION DEVICES.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717