Plan Review Notes
Plan Review Notes For Permit 09080706
Permit Number 09080706
Review Stop B
Sequence Number 1
Notes
Date Text
2009-09-14 11:22:02****CORRECTIONS****
 ****MASTER/PROJECT ONLY (INSPECTION HOLD PLACED ON THIS
 PERMIT)****
 ****APPLICATION BY CONTRACTOR REQUIRED PRIOR TO PERMIT
 ISSUANCE****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. ONE OF THE SETS IS NOT SIGNED AND SEALED BY THE
 ARCHITECT, FS481.
  
 2. THE PLANS SHOW WINDOWS A AND B AT BEDROOMS AS
 "EGRESS" AND SHEET A2.1 INCLUDES A NOTE STATING THAT
 THE BEDROOM WINDOWS WILL COMPLY WITH FBC1026. THE
 WINDOWS ARE 4'3", 4'5", AND 3' IN HEIGHT; IT APPEARS
 THAT NONE COMPLY WITH THE HEIGHT REQUIREMENT OF 24".
 SEE FBC EXISTING BUILDING 604.1 TO SEE EXCEPTION. THE
 WINDOWS PROPOSED MAY MEET THE EXCEPTION, BUT IN THAT
 CASE PLEASE REMOVE OR REVISE THE NOTES REGARDING EGRESS
 AND MAKE NOTE ON THE PLAN OF THE WINDOW TYPE OF THE
 EXISTING WINDOWS.
  
 3. DETAILS 2 AND 3, SHEET A3.1, BOND BREAK REQUIRED FBC
 R 703.6.3; PLEASE REVISE AND CHECK ALL.
  
 4. DETAILS 2 AND 3, SHEET A3.1, A MINIMUM OF 1 3/4"
 PENETRATION REQUIRED INTO STRUCTURAL MEMBER (ASTM
 C1063); A 1 1/4" NAIL IS SPECIFIED, FBC R 703.6.2;
 PLEASE REVISE AND CHECK ALL.
  
 5. CASEMENT WINDOW PRODUCT APPROVALS WERE SUBMITTED,
 BUT ARE NOT SHOWN AS AN OPTION ON THE PLAN. ONLY SINGLE
 HUNG WINDOWS WERE SPECIFIED.
  
 6. BINDER TAB #4, AWP SERIES 1700, THE NOA IS EXPIRED.
  
 7. BINDER TABS #5 AND #8, EFCO WINDOWS, AND #9 PGT
 MULLION; THE FLORIDA STATE PRODUCT APPROVALS ARE
 EXPIRED (2004 CODE RATHER THAN 2007), BUT THE NOAS ARE
 CURRENT. THE FLORIDA STATE PRODUCT APPROVAL COVER
 SHEETS WILL BE REMOVED; NO ACTION REQUIRED
 (INFORMATIONAL ONLY).
  
 8. BINDER TAB #10, FLEMING DOOR, PRODUCT APPROVAL IS
 EXPIRED (2004 CODE RATHER THAN 2007). PROVIDE CURRENT
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL FAC9B72.
  
 9. BINDER TAB #11, WOOD CONNECTORS, PRODUCT APPROVAL IS
 EXPIRED (2004 CODE RATHER THAN 2007). ALSO NOTE THAT
 ONLY THE PRODUCT APPROVAL FOR L70 WAS PROVIDED. PLEASE
 PROVIDE EITHER SPEC SHEETS (WITH INSTALLATION
 INSTRUCTIONS) AND PRODUCT APPROVAL NUMBERS FOR ALL OF
 THE CONNECTORS OR INCORPORATE THE INFORMATION INTO THE
 PLAN.
  
 10. PLEASE NOTE THAT ONE PERMIT IS REQUIRED FOR EACH
 PARCEL ID. IF MORE THAN ONE STRUCTURE IS INCLUDED ON A
 PARCEL, THE CONTRACTOR MAY REQUEST A SEPARATE PERMIT
 FOR EACH STRUCTURE, BUT THIS IS NOT REQUIRED. THE
 CONTRACTOR MAY WISH TO FACILITATE TRACKING OF
 INSPECTIONS.
  
 11. SPEC SHEETS AND FLORIDA STATE PRODUCT APPROVAL
 COVER SHEETS (EXPIRED) FOR AWP WINDOWS WERE INCLUDED IN
 THE INSIDE POCKET OF THE BINDERS. THESE DOCUMENTS WILL
 BE DISCARDED; NO ACTION REQUIRED (INFORMATIONAL ONLY).
  