Plan Review Notes For Permit 09080705
Permit Number 09080705
Review Stop B
Sequence Number 2
Notes
Date Text
2009-09-23 13:18:24BUILDING REVISIONS REQUIRED
  
 1) THE FLAT ROOF UPLIFT PRESSURES AND RAS 117
 CALCULATIONS ON SHEET A2.3 ARE REQUIRED TO BE REVISED
 TO EXPOSURE C.
  
 2) THE DESIGN PRESSURES LISTED IN THE PRODUCT APPROVAL
 FOR THE THERMA-TRU SINGLE OUTSWING GLAZED DOOR OF + / -
 47 ARE LOWER THAN THE REQUIRED COMPONENT AND CLADDING
 NEGATIVE PRESSURE OF -49.5 SPECIFIED ON THE PLANS.
 PROVIDE PRODUCT APPROVALS FOR DOOR WITH ADEQUATE DESIGN
 PRESSURES.
  
 3) THE DOUBLE OUTSWING OPAQUE OUTSWING DOOR THAT WAS
 CLOUDED ON THE PRODUCT APPROVAL WITH DESIGN PRESSURES
 OF + /- 40 IS TOO LOW. HOWEVER, THE ONE WITH THE
 COASTAL ALUMNIUM ASTRAGAL HAS DESIGN PRESSURES OF +/-
 55 AND DO MEET THE REQUIRED OPENING PRESSURES.