| Plan Review Notes For Permit 09080705 |
| Permit Number |
09080705 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-09-23 13:18:24 | BUILDING REVISIONS REQUIRED | | | | | | 1) THE FLAT ROOF UPLIFT PRESSURES AND RAS 117 | | | CALCULATIONS ON SHEET A2.3 ARE REQUIRED TO BE REVISED | | | TO EXPOSURE C. | | | | | | 2) THE DESIGN PRESSURES LISTED IN THE PRODUCT APPROVAL | | | FOR THE THERMA-TRU SINGLE OUTSWING GLAZED DOOR OF + / - | | | 47 ARE LOWER THAN THE REQUIRED COMPONENT AND CLADDING | | | NEGATIVE PRESSURE OF -49.5 SPECIFIED ON THE PLANS. | | | PROVIDE PRODUCT APPROVALS FOR DOOR WITH ADEQUATE DESIGN | | | PRESSURES. | | | | | | 3) THE DOUBLE OUTSWING OPAQUE OUTSWING DOOR THAT WAS | | | CLOUDED ON THE PRODUCT APPROVAL WITH DESIGN PRESSURES | | | OF + /- 40 IS TOO LOW. HOWEVER, THE ONE WITH THE | | | COASTAL ALUMNIUM ASTRAGAL HAS DESIGN PRESSURES OF +/- | | | 55 AND DO MEET THE REQUIRED OPENING PRESSURES. |
|