| Plan Review Notes For Permit 09080705 |
| Permit Number |
09080705 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-01 13:27:21 | PROVISO | | | | | | DINING ROOM RECEPTACLE SPACING PER 210.52.SHEET E1.1. | | | | | | SHEET E2.1 | | | | | | NO 80 AMP AS PER NOTE #13 ON RISER AND NO SCHEDULE FOR | | | SAME. | | | | | | ALL BATH RECEPTACLE CIRCUITS PER 210.11(C)(3). | | | | | | DINING ROOM CIRCUITS PER 210.52(B)(1)-20 AMP SMALL | | | APPLIANCE. | | | | | | AC-AHU #2 SHOWN LOCATED IN PANEL "A" AND "DP" | | | | | | AHU 1 & 2 DO NOT CORRELATE WITH THE RATINGS GIVEN ON | | | SHEET M1.1 |
|