Plan Review Notes
Plan Review Notes For Permit 09080705
Permit Number 09080705
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-01 13:27:21PROVISO
  
 DINING ROOM RECEPTACLE SPACING PER 210.52.SHEET E1.1.
  
 SHEET E2.1
  
 NO 80 AMP AS PER NOTE #13 ON RISER AND NO SCHEDULE FOR
 SAME.
  
 ALL BATH RECEPTACLE CIRCUITS PER 210.11(C)(3).
  
 DINING ROOM CIRCUITS PER 210.52(B)(1)-20 AMP SMALL
 APPLIANCE.
  
 AC-AHU #2 SHOWN LOCATED IN PANEL "A" AND "DP"
  
 AHU 1 & 2 DO NOT CORRELATE WITH THE RATINGS GIVEN ON
 SHEET M1.1