| Plan Review Notes For Permit 09080638 |
| Permit Number |
09080638 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-08 12:01:02 | *****DENIED***** | | | | | | | | | 1. ONLY ONE PLAN SET WAS SUBMITTED. AT LEAST TWO, NO | | | MORE THAN THREE PLAN SETS SHALL BE SUBMITTED. | | | | | | 2. THE PLANS/DRAWINGS SHALL BE PRESENTED WITH NO INK, | | | PENCIL, OR ANY OTHER MARKINGS. | | | | | | 3. SINCE THE SUBMITTED PLAN SHEETS CONTAIN THE DESIGNER | | | OF RECORD, THE DOCUMENT SHALL BE STAMPED, SIGNED, AND | | | SEALED BY THE ENGINEER WHOSE NAME APPEARS ON THE TITLE | | | BLOCK. | | | | | | 4. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | | REFERENCED. | | | | | | 5. PROVIDE SPEC SHEETS (AND/OR INCLUDE IN THE PLAN) AS | | | TO HOW THE DELAYED-EGRESS LOCK AND/OR ACCESS-CONTROLLED | | | EGRESS DOOR(S) SHALL COMPLY WITH 7.2.1.6 OF NFPA 101 - | | | LIFE SAFETY CODE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | |
|