Plan Review Notes
Plan Review Notes For Permit 09080638
Permit Number 09080638
Review Stop E
Sequence Number 1
Notes
Date Text
2009-09-02 14:49:40 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS,
 AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS
 WITH EACH APPLICATION FOR A PERMIT.
  
 2} THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED
 TO REVISE HIS/HER PLAN. TAKE ALL PROPOSED CHANGES TO
 THE DESIGNER TO BE REDRAWN. THE ENGINEER WHOSE NAME
 APPEARS ON THE TITLE BLOCK MUST SIGN, DATE AND SEAL THE
 DOCUMENT. 61G15-23.002 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  