| Plan Review Notes For Permit 09080618 |
| Permit Number |
09080618 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-09-14 13:45:07 | PROVISO | | | REVISION REQUIRED | | | | | | 1. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW | | | COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE | | | INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS. | | | THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL. | | | | | | 2. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT | | | FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER | | | (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO | | | HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT | | | WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE | | | LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT | | | BE NOTARIZED. | | | | | | 3. FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE | | | FABRIC MEETS THE REQUIREMENT OF NFPA701. | | | | | | ***IT IS ADVISED THAT CONTRACTOR ADDRESS THESE COMMENTS | | | WHEN RESUBMITTING; OTHERWISE, A REVISION WILL BE | | | REQUIRED BEFORE FIRST INSPECTION*** |
|