| Date |
Text |
| 2010-01-20 09:07:24 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 BUILDING |
| | FBC-2007 CHAPTER 1 |
| | FBC-2007 CHAPTER 11 |
| | FBC-2007 EXISTING BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. COVER SHEET INDICATES EXISTING RESTAURANT AREA. THIS |
| | IS NOT SHOWN ON THE PLANS. PLEASE SHOW THE EXISTING |
| | KITCHEN AREA, OR IF THE KITCHEN AREA IS TO BE DEMO'D |
| | PLEASE INDICATE. SECTION 106.1.2 (MORE INFORMATION |
| | REQUIRED). IF DEMOLITION OF THE KITCHEN AREA, THEN |
| | DEMOLITION WORK SHALL BE SHOWN ON THE PLANS OR A |
| | SEPARATE DEMO PERMIT WITH PLANS WILL BE REQUIRED. |
| | SECTION 105.1. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. PLEASE SUBMIT |
| | AN EXISTING FLOOR PLAN TO VERIFY ALL WORK TO BE DONE ON |
| | THIS PROJECT. |
| | |
| | 2. OK |
| | 3. OK |
| | |
| | 4. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED FOR ALL |
| | NEW WORK. SECTION 106.3.5.1.3(3)(5)((10)(13). |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 5. PER TABLE 403.1 A SERVICE SINK AND A DRINKING |
| | FOUNTAIN ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH |
| | REQUIRED FIXTURE. |
| | ****NO RESPONSE, BUT A MOP SINK IS INDICATED ON THE |
| | FLOOR PLAN NEW SHEET A101. THE REQUIREMENT FOR THE |
| | DRINKING FOUNTAIN IS ADDRESSED WITH EXCEPTION IN |
| | SECTION 4101. |
| | |
| | 6. A WATER HEATER IS REQUIRED PER SECTION 607.1. PLEASE |
| | SHOW THE LOCATION OF THE REQUIRED WATER HEATER. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 7. BECAUSE OF THE LACK OF INFORMATION ON PLANS, |
| | DEPENDING ON COMMENT RESPONSES, MORE COMMENTS MAY BE |
| | FORTHCOMING. |
| | ****SEE NEW COMMENTS. |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. COVER SHEET SEATING CAPACITY TOTAL OF 184, BUT A |
| | COUNT OF ALL SEATS INCLUDING THOSE ON THE EXISTING |
| | PATIO INDICATES 210 SEATS. PLEASE CLARIFY. |
| | |
| | 2B. SHT A101 IS NOT SIGNED, SEALED AND DATED AS |
| | REQUIRED IN SECTION 106.1 OF THE FBC ADMINISTRATION AS |
| | WELL AS FAC 61G1-16 & FS 481.2055. |
| | |
| | 3. SHT A101 SHOWS THE WOMEN'S TOILET ROOM BEING |
| | ALTERED. PER SECTION 11-4.1.6(1)(B) IF EXISTING |
| | ELEMENTS, SPACES, OR COMMON AREAS ARE ALTERED, THEN |
| | EACH SUCH ALTERED ELEMENT, SPACE, FEATURE, OR AREA |
| | SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION |
| | 11-4.1.1 TO SECTION 11-4.1.3. THE WOMEN'S ACCESSIBLE |
| | STALL SHALL COMPLY WITH FIGURE 11-30(E). |
| | |
| | 4B. SHT P100 SHOWS A GREASE INTERCEPTOR. IS THIS AN |
| | EXISTING INTERCEPTOR. INDICATE THE SIZE OF THE |
| | INTERCEPTOR. SECTION 1003.1. |
| | |
| | 5B. SHT P100 SANITARY/GREASE RISER DIAGRAM, WASTE THAT |
| | DO NOT REQUIRE SEPARATION OR TREATMENT SHALL NOT BE |
| | DISCHARGE INTO ANY SEPARATOR OR INTERCEPTOR. THE FLOOR |
| | SINKS USED FOR DRAINING THE COOLERS & RINSE SINKS IN |
| | THE BAR AREA SHALL BE DISCHARGED TO THE SANITARY |
| | SYSTEM. SECTION 1003.2. |
| | |
| | 6B. SHT P100 SANITARY/GREASE RISER DIAGRAM. THE MOP |
| | SINK SHALL DRAIN INTO THE GREASE INTERCEPTOR. SECTION |
| | 1003.3.3.1. (NOT SHOWN ON RISER DIAGRAM). |
| | |
| | 7B. SHT P100 SANITARY/GREASE RISER DIAGRAM SHOWS A VENT |
| | DOWNSTREAM OF THE FLOOR SINKS AT THE BAR. PER SECTIONS |
| | 905.3 & 905.4 THE VENT SHALL BE CONNECTED ABOVE THE |
| | CENTERLINE OF THE HORIZONTAL DRAIN PIPE AND SHALL RISE |
| | VERTICALLY A MINIMUM OF 6" ABOVE THE FLOOD RIM LEVEL OF |
| | THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| | |
| | 8B. SHT P100 SANITARY/GREASE RISER DIAGRAM DOES NOT |
| | REFLECT THE CHANGES INDICATED IN THE WOMEN'S TOILET |
| | ROOM. |
| | |
| | 9B. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT |
| | APPLICATION AND PLANS PRIOR TO COMMENCING GAS WORK. |
| | SECTION 105.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. (NO WRITTEN |
| | RESPONSE SUBMITTED). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |