| Date |
Text |
| 2009-09-10 09:08:51 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 BUILDING |
| | FBC-2007 CHAPTER 1 |
| | FBC-2007 CHAPTER 11 |
| | FBC-2007 EXISTING BUILDING |
| | |
| | 1. COVER SHEET INDICATES EXISTING RESTAURANT AREA. THIS |
| | IS NOT SHOWN ON THE PLANS. PLEASE SHOW THE EXISTING |
| | KITCHEN AREA, OR IF THE KITCHEN AREA IS TO BE DEMO'D |
| | PLEASE INDICATE. SECTION 106.1.2 (MORE INFORMATION |
| | REQUIRED). IF DEMOLITION OF THE KITCHEN AREA, THEN |
| | DEMOLITION WORK SHALL BE SHOWN ON THE PLANS OR A |
| | SEPARATE DEMO PERMIT WITH PLANS WILL BE REQUIRED. |
| | SECTION 105.1. |
| | |
| | 2. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER |
| | TABLES 1004.1.1 (BLDG) & 403.1 (PLUMBING). IF ASSEMBLY |
| | WITH FIXED SEATS, (SECTION 1004.7), SHOW THE FIXED |
| | SEATING. IF ASSEMBLY CONCENTRATED, (CHAIRS ONLY - NOT |
| | FIXED), SHOW THE CHAIRS. IF ASSEMBLY STANDING SPACE. |
| | PLEASE INDICATE. IF ASSEMBLY UNCONCENTRATED, (TABLES & |
| | CHAIRS), SHOW THE TABLES & CHAIRS. SECTIONS 1004 & |
| | 403.. |
| | |
| | 3. SHT A.02 MEN'S TOILET ROOM SHOWS THE EXISTING STALL |
| | WITH A LAV, BUT SHT A.03 SHOWS THE NEW STALL WITHOUT |
| | THE LAV. PER SECTION 11-4.1.6(1)(A), NO ALTERATION |
| | SHALL BE UNDERTAKEN WHICH DECREASES OR HAS THE EFFECT |
| | OF DECREASING ACCESSIBILITY OR USABILITY OF A BUILDING |
| | OR FACILITY BELOW THE REQUIREMENT FOR NEW CONSTRUCTION |
| | AT THE TIME OF ALTERATION. PER SECTION 11-4.1.6(1)(B) |
| | IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE |
| | ALTERED, THEN EACH SUBH ALTERED ELEMENT, SPACE, |
| | FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE |
| | PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3., |
| | MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. |
| | |
| | 4. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED FOR ALL |
| | NEW WORK. SECTION 106.3.5.1.3(3)(5)((10)(13). |
| | |
| | 5. PER TABLE 403.1 A SERVICE SINK AND A DRINKING |
| | FOUNTAIN ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH |
| | REQUIRED FIXTURE. |
| | |
| | 6. A WATER HEATER IS REQUIRED PER SECTION 607.1. PLEASE |
| | SHOW THE LOCATION OF THE REQUIRED WATER HEATER. |
| | |
| | 7. BECAUSE OF THE LACK OF INFORMATION ON PLANS, |
| | DEPENDING ON COMMENT RESPONSES, MORE COMMENTS MAY BE |
| | FORTHCOMING. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |