| 2010-01-21 08:39:56 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. FLOOR PLAN INDICATES CEILING MOUNTED EXHAUST FANS TO |
| | BE USED IN RESTROOMS. HOWEVER, NOTES ON FAN SCHEDULE |
| | CALL FOR A SOUND ATTENUATED ROOF CURB AND DETAIL ON |
| | PAGE M102 SHOWS A ROOF MOUNTED FAN. PLEASE COORDINATE |
| | FLOOR PLANS, SCHEDULE NOTES AND DETAILS TO SHOW ACTUAL |
| | SCOPE OF WORK IN ACCORDANCE WITH FBC-B 106.1.1. |
| | |
| | 2. A/C EQUIPMENT SCHEDULE SHOWS FOUR RTU'S WHILE THE |
| | FLOOR PLAN SHOWS FIVE RTU'S. ALSO, SCHEDULE SHOWS SPLIT |
| | SYSTEM AC-1, WHILE FLOOR PLAN SHOWS AH-5. PLEASE |
| | COORDINATE FLOOR PLANS AND SCHEDULE TO SHOW ACTUAL |
| | SCOPE OF WORK IN ACCORDANCE WITH FBC-B 106.1.1. |
| | |
| | 3. LOCATION OF CONDENSER FOR SPLIT A/C SYSTEM IS NOT |
| | SHOWN ON PLANS. SHOW THE LOCATION WITH WIND RESISTANT |
| | INSTALLATION DETAILS IN ACCORDANCE WITH FBC-M 301.12. |
| | |
| | 4. PROVIDE MANUFACTURER'S WIND RESISTANCE DATA FOR ALL |
| | OUTDOOR APPLIANCES AND EQUIPMENT EXPOSED TO WIND, SUCH |
| | AS RTU'S, ROOF CURBS/CAPS, CONDENSERS, FANS, ETC. IN |
| | ACCORDANCE WITH FBC-M 301.12. |
| | |
| | 5. SHOW LOCATION OF DUCT SMOKE DETECTORS ON PLANS IN |
| | ACCORDANCE WITH FBC-M 606.2.1. |
| | |
| | 6. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN |
| | ACCORDANCE WITH FBC-M 307.2.1. |
| | |
| | NOTE: SEPARATE PLANS AND PERMIT APPLICATIONS SHALL BE |
| | SUMITTED FOR THE FOLLOWING: |
| | COMMERCIAL KITCHEN EXHAUST SYSTEM |
| | HOOD FIRE SUPPRESSION SYSTEM |
| | WALK-IN COOLER AND FREEZER |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |