| 2009-09-18 20:01:00 | |
| | ** DENIED ** |
| | |
| | ** REVIEW IS BASED ON PLANS AND SUPPORTING DOCUMENTS |
| | SUBMITTED. |
| | |
| | 1) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING |
| | RELEVANT CODES. |
| | 2006 NFPA-101 |
| | 2005 NFPA-70 |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | ** PLEASE PROVIDE MORE INFORMATION ON ELECTRICAL PLANS. |
| | THE FOLLOWING IS NOTED AS THERE ARE ITEMS NOT YET |
| | SUBMITTED. |
| | |
| | 2) NOTE: PLEASE SEE 13-415.AB.1.4 FOR EXTERIOR LIGHTING |
| | CONTROLS. |
| | |
| | 3) NOTE: PLEASE PROVIDE NEW AND EXISTING LIGHTING |
| | LOCATIONS. NEED TO VERIFY LIGHTING FOR EGRESS |
| | REQUIREMENTS OF LOCATION. NEW AREAS APPEAR TO MEET |
| | MINIMUM LEVELS UNDER BATTERY BACK UP PER NFPA- 101 |
| | 7.8.1.3,7.9.1.2,7.9.2.2, FBC 1006.1.2 |
| | PLEASE PROVIDE LIGHTING NEW OR EXISTING FOR BATHROOMS. |
| | |
| | 4) NOTE: PLEASE SURE TO SHOW CIRCUITING ON PLANS FOR |
| | NEW. PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND |
| | EXIT LIGHTS. |
| | |
| | 5) NOTE: PLANS STATE NEW SIGN. PLEASE SEE 600.5 FOR |
| | REQUIRED DEDICATED SIGN CIRCUIT TO BE SHOWN ALONG WITH |
| | LOAD PER SAME SECTION. MINIMUM OF 1200VA REQUIRED. |
| | |
| | 6) NOTE: PLEASE PROVIDE PANEL SCHEDULE OR NOTE NEW |
| | CIRCUITS. 408.4. |
| | |
| | 7) NOTE: PLEASE PROVIDE THE LATEST ELECTRICAL RISER FOR |
| | RECENT SERVICE CHANGE DONE ON PLANS. |
| | 215.5,230.2, 240.4,310.16, 230.70. |
| | |
| | ** SOME OF THE ABOVE ITEMS COULD BE SET UP AS A |
| | PROVISO. PLEASE CALL TO GO OVER. |
| | |
| | |
| | ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT |
| | INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS |
| | REQUIRED. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |